Mitsubishi Electric Lossnay PZ-70CSW-E Installation And Instruction Manual

Mitsubishi Electric Lossnay PZ-70CSW-E Installation And Instruction Manual

Co2 sensor wall-mounting type

Advertisement

Quick Links

Lossnay CO
Sensor Wall-Mounted Type
2
PZ-70CSW-E
Installation and Instruction Manual
This CO
sensor changes the color of its LED light in accordance with the CO
2
reduces the fresh air load.
■ This manual must be read both fully and carefully before commencing installation procedures; furthermore, the subsequent installation must be
performed correctly and safely in accordance with the instructions given.
■ After installation, ensure that this manual is given to the customer.
1. Safety Precautions
WARNING
- Never modify or repair by yourself.
If the product is modified or inappropriately repaired, electric shock, fire, etc. could result. Contact your dealer for repair.
- Do not move or reinstall the product by yourself.
If it is installed improperly, electric shock, fire, etc. could result. Contact your dealer or technical representative.
- Use the specified cables for wiring and connect them securely. Hold the cables so as not to apply external force of the cables to the
connector.
Improper connection could result in heat generation or fire.
- All electrical work must be performed by a licensed technician, according to local regulations and the instructions given in this Installation
manual.
- Install the product in a firm and stable place to withstand the product weight.
If the strength is inadequate, the product could drop and cause an injury.
- Ensure that installation work is done correctly following this Installation manual.
If it is installed improperly, electric shock, fire, etc. could result.
- Close the control cover after installation.
- Do not install the product in a place where flammable gases may leak.
If gas should leak or accumulate around the product, fire or explosion could result.
- Do not use the product in special environments.
The product could be damaged if it is used in locations subject to large quantities of oil (including machine oil), steam, or sulfide gas.
- Do not install the unit in a place where the temperature rises above 40 ˚C (104°F), where large amounts of oil, steam, organic solvents, or
corrosive gases, such as sulfuric gas, are present, or where acidic/alkaline solutions or sprays are used frequently.
These substances can compromise the performance of the unit or cause certain components of the unit to corrode, which can result in electric shock,
malfunctions, smoke, or fire.
- Do not install the product in a place where highly humid, like a bathroom, or other wet place.
It could cause electric shock or injury.
CAUTION
- Wire so that it does not receive any tension.
Tension could cause wire breakage, heating or fire.
- Seal the cable from the sensor case with putty etc.
Any dew, moisture, cockroaches, insects entering the unit could cause electric shock or malfunctions.
- Put on gloves during installation.
Failure to do so could cause injury.
- To avoid discoloration, do not use benzene, thinner, ethanol,hypochlorous acid or chemical rag to clean the case. To clean the case, wipe
with a soft cloth soaked in water with mild detergent, wipe off the detergent with a wet cloth, and wipe off water with a dry cloth.
Incorrect handling could cause serious injury or death.
Incorrect handling could cause injury or damage to property or household effects.
concentration within the room, optimizes the amount of airflow, and thus
2
1
2107876H65401

Advertisement

loading

Summary of Contents for Mitsubishi Electric Lossnay PZ-70CSW-E

  • Page 1 2107876H65401 Lossnay CO Sensor Wall-Mounted Type PZ-70CSW-E Installation and Instruction Manual concentration within the room, optimizes the amount of airflow, and thus This CO sensor changes the color of its LED light in accordance with the CO reduces the fresh air load. ■...
  • Page 2: Specifications

    2. O utline drawings, Included Accessories, and Specifications ■ Included accessories ■ Outline drawings Please confirm that the following accessory parts are included in the box. 1. Sensor case (top case, bottom case): x 1 70(2 3/4) 26(1 1/32) 2. Cross-slot pan-head screws M4x30: x 2 3.
  • Page 3 3.2 W hen using cable extensions and external bypass switching <items to carry out if necessary> ■ Cable extension Depending on the installation location, extensions for the included cables may be necessary. Extension up to 20 m (22 yards), including the included cables is possible. <Required items> - Cable (non-polar 4-wire sheathed 0.3 mm (AWG 22) cable (conductor resistance of 60 Ω/km or less)) - Crimped terminal * Two sets of above items are required—one each for the CO sensor cable and for the LED cable.
  • Page 4 3.4 Open the sensor case Insert a flat-head screwdriver into the tab, and push this down to remove the top case. Bottom case Cable access hole Top case Note: - Remove the case, taking care not to damage it. - Do not turn the flat-head screwdriver while it is inserted in the tab. Doing so may damage the tab or the case. sensor cables through the cable access hole in the bottom case 3.5 Pass the LED and CO Pull each cable through from the switch box or wall, and pass through the cable access hole in...
  • Page 5: Wiring Diagram

    3.9 Fit the top case to the bottom case The top case has two tabs at its top. Hook these tabs into the bottom case, and push until a “click” is heard. Note: Bottom case - Attach the top case while making sure that leads are not caught. - Push until a “click”...
  • Page 6 6.3 Auto fan speed setting without Lossnay or M-NET centralized remote controller If not connecting remote controllers or M-NET centralized controllers to the Lossnay unit, set the “Auto fan speed setting without Lossnay or M-NET centralized remote controller” dip switch to ON. 6.4 CO sensor setting - maximum side and minimum side concentration are selectable. The upper and lower limit of CO The Lossnay unit controls its fan speed according to the set upper and the lower limit.
  • Page 7: Manual Download

    (3) Threshold minutes The threshold time at which the LED changes from “MID (orange)” to “HIGH (red)” can be set within the range of 10 to 30 minutes. (settable in 5-minute increments) The factory default setting is “20 min.” For how to configure the setting, refer to “Threshold minutes for PZ-70CSW-E LED” in the Installation Instructions for the Lossnay unit. 7.