PZ-70CSB-E
Installation and Instruction Manual
sensor optimizes the amount of airflow in accordance with the CO
This CO
2
■ This manual must be read both fully and carefully before commencing installation procedures; furthermore, the subsequent installation must be
performed correctly and safely in accordance with the instructions given.
■ After installation, ensure that this manual is given to the customer.
1. Safety Precautions
WARNING
- Never modify or repair by yourself.
If the product is modified or inappropriately repaired, electric shock, fire, etc. could result. Contact your dealer for repair.
- Do not move or reinstall the product by yourself.
If it is installed improperly, electric shock, fire, etc. could result. Contact your dealer or technical representative.
- Use the specified cables for wiring and connect them securely. Hold the cables so as not to apply external force of the cables to the
connector.
Improper connection could result in heat generation or fire.
- All electrical work must be performed by a licensed technician, according to local regulations and the instructions given in this Installation
manual.
- Ensure that installation work is done correctly following this Installation manual.
If it is installed improperly, electric shock, fire, etc. could result.
- Close the control cover after installation.
- Do not install the product in a place where flammable gases may leak.
If gas should leak or accumulate around the product, fire or explosion could result.
- Do not use the product in special environments.
The product could be damaged if it is used in locations subject to large quantities of oil (including machine oil), steam, or sulfide gas.
- Do not install the unit in a place where the temperature rises above 40 ˚C (104°F), where large amounts of oil, steam, organic solvents, or
corrosive gases, such as sulfuric gas, are present, or where acidic/alkaline solutions or sprays are used frequently.
These substances can compromise the performance of the unit or cause certain components of the unit to corrode, which can result in electric shock,
malfunctions, smoke, or fire.
CAUTION
- Wire so that it does not receive any tension.
Tension could cause wire breakage, heating or fire.
- Put on gloves during installation.
Failure to do so could cause injury.
Incorrect handling could cause serious injury or death.
Incorrect handling could cause injury or damage to property or household effects.
concentration within the room, and thus reduces the fresh air load.
2
1
2107876H65301

Advertisement

loading

Summary of Contents for Mitsubishi Electric PZ-70CSB-E

  • Page 1 2107876H65301 Lossnay CO Sensor Built-In Type PZ-70CSB-E Installation and Instruction Manual sensor optimizes the amount of airflow in accordance with the CO concentration within the room, and thus reduces the fresh air load. This CO ■ This manual must be read both fully and carefully before commencing installation procedures; furthermore, the subsequent installation must be performed correctly and safely in accordance with the instructions given.
  • Page 2: Installation Method

    2. E xternal Dimensions, 3. Installation Method Included Accessories, * Refer to the Operation Instructions and Installation instructions of Lossnay unit. and Specifications * Figures show the installation method of LGH-RVS series. 3.1 Before installation (1) Remove the Lossnay unit control box cover. ■ Included accessories Control box cover Please confirm that the following accessory parts are included in the box.
  • Page 3: Wiring Diagram

    Once installation work is complete, confirm again that wiring is as per the position. wiring diagram, and that no parts or screws remain unused. - Do not disconnect connectors that are already connected. Communication cables hole PZ-70CSB-E Lossnay unit control circuit board CN23 CN35 sensor cable Note: - Return the packing so that it does not come off the Lossnay unit.
  • Page 4 4.2 Collecting excess cable 5. Precautions (1) Collect excess cable using the cord clip included with the Lossnay unit. Airflow function (unbalanced supply and exhaust air flow setting) is not available during the Lossnay unit fan speed is controlled by CO sensor. Cord clip - CO concentrations will differ depending on the usage environment and product installation conditions, therefore the value measured by the CO sensor may differ from the actual CO concentration within the room.
  • Page 5 Lossnay unit, keep “CO sensor or BMS setting” in all Lossnay units to “PZ-70CSB-E connection,” and set “Input priority setting" to “Individual control priority.” - If using a remote controller, configure 6.4. CO sensor setting - maximum side and minimum side.
  • Page 6: Trial Operation

    6.7 CO concentration correction sensor detects CO concentration at the RA path in the Lossnay unit and CO concentration within the room varies. The CO Thus, the CO concentration values displayed on the remote controller may differ from CO concentration values detected by environment measuring instruments.