8.2.2 Display of detailed information on a past trip

Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the     key when the
trip record is selected in the status monitor mode.
Unlike the "Display of detailed trip information at the occurrence of a trip" in 8.2.2, details on a past trip can be displayed,
even after the inverter is turned off or reset.
Item displayed
[Note 6]
Past trip 1
Continuous trips
[Note 1]
Operation frequency
Status monitor mode
(Rotating direction)
Operation frequency
command
Load current
[Note 2]
[Note 3]
DC voltage
Output voltage
*6
Torque
Regenerative
*7
braking resistance
Inverter overload
*8
factor
*9
Peak output current
8
Input terminal
[Note 4]
information 1
Input terminal
[Note 4]
information 2
Input terminal
[Note 4]
information 3
Output terminal
[Note 5]
information 1
Output terminal
[Note 5]
information 2
Cumulative operation
[Note 7]
time
Past trip 1
Note 1: Press the
Note 2: You can switch between % and A (ampere)/V (volt), using the parameter  (current/voltage unit selection).
Note 3: The input voltage displayed is 1/√2 times as large as the rectified DC input voltage.
Note 4: The number of bars displayed varies according to the setting of SW4. The RR/S4 bar is displayed only when the
contact input function is assigned.
If SW4 is in the RR position : The RR/S4 bar is not displayed.
If SW4 is in the S4 position : The RR/S4 bar is displayed.
Key
LED display
operated
⇔  Past trip 1 (displayed alternately.)
The number of time the same trip occurred in succession is displayed.
ENT

(Unit: times)
The operation frequency when the trip occurred is displayed.


The direction of rotation is displayed. (  :Forward run,  :Reverse run)
The operation frequency command value is displayed.

(When F711=1, operation frequency command)
The inverter output current (load current) is displayed.

(When F712=2, current display)
The inverter DC voltage is displayed. (Default setting unit: % )

(When F713=3, DC voltage) [Note 3]
The inverter output voltage is displayed. (Default setting unit: % )

(When F714-=4, output voltage)
The torque is displayed.

(When F715=8, torque)
The regenerative braking resistance overload factor is displayed.

(When F716=16, regenerative braking resistance overload factor)
The inverter overload factor is displayed.

(When F717=15, inverter overload factor)
The peak output current is displayed. (Default setting unit: %)

(When F718=20, peak output current)
The ON/OFF status of each of the control signal input terminals (F, R,

RES, ST, S1, S2, S3, RR/S4) is displayed in bits.
The ON/OFF status of each of the optional control signal input

terminals (L1, L2, L3, L4) is displayed in bits.
The ON/OFF status of each of the optional control signal input

terminals (L5, L6, L7, L8) is displayed in bits.
The ON/OFF status of each of the control signal output terminals
  
(OUT1, OUT2, FL) is displayed in bits.
The ON/OFF status of each of the control signal output terminals

(OUT3, OUT4, R1, OUT5, OUT6, R2, R3, R4) is displayed in bits.
The cumulative operation time when the trip occurred is displayed.

(0.01=1 hour, 1.00=100 hours)
 ⇔ 
Press this key to return to past trip 1.
MODE
   or    key to change items displayed in the status monitor mode.
Description
H-6
E6581301
ENT