MITSUBISHI ELECTRIC / OPTIONAL PARTS
MAC-334IF
Output signals
Please, use the camble of 0,5mm
The cable must fit into TB530
and meet DC12V supply.
M-Net2 M-Net1
B2 A2 B1
A1
S
TB520
TB521
SW500
1
2
3
4
5
6
7
8
SW502
1
2
3
4
5
6
7
8
(M-Net)
(Orange)
(Red)
MA
SW580
LE501
LE502
SW501 SW510
No.
FINCTIONS
ON/OFF,
1
Error/
Normal output
ON/OFF,
2
Heater control output
ON/OFF,
3
Humidifier control output
Heater control,
4
Humidifier control output
ON/OFF,
5
Humidifier control
(single operation output)*
88
or more.
2
R1
R2
C
-
+
B
A
TB580
TB571
TB530
(Grey)
(Sky Blue)
CN591
(Orange)
(White)
3 2 1
LE581
CN560
(White)
MAC-334IF-E
SW No.
SW500
1
2
3
4
5
6
7
8
SW502
1
2
3
4
5
6
7
8
SW500
1
2
3
4
5
6
7
8
SW502
1
2
3
4
5
6
7
8
SW500
1
2
3
4
5
6
7
8
SW502
1
2
3
4
5
6
7
8
SW500
1
2
3
4
5
6
7
8
SW502
1
2
3
4
5
6
7
8
SW500
1
2
3
4
5
6
7
8
SW502
1
2
3
4
5
6
7
8
-
+
Supply
DC
12V
Supply power DC 12 V
(+10%, -0%) at least 5W.
Please use power supply
with double insulation or
reinforced insulation
SW502-1: OFF
• Relay 1 is on when room ai conditioner is on, and off when room air conditioner is off
• Relay 2 is on when room air conditioner isin error, and off when room air conditioner is operating
normally
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above
SW502-1: OFF
• Relay 1 is on when room ai conditioner is on, and off when room air conditioner is off
• When the air conditioner runs in the heating (automatic heating) mode and room temperature
becomes the set temperature - 2.5 °C (4.5 °F) or lower, the Relay 2 (heater) turns on.
When the air conditioner runs in a mode other than the heating (automatic heating) or it is OFF,
or when room temperature becomes the set temperature or higher, the Relay 2 (heater) turns off
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above
SW502-1: OFF
• Relay 1 is on when room ai conditioner is on, and off when room air conditioner is off
• When the air conditioner runs in the heating (automatic heating) mode, Relay 2 (humidifier) turns on.
When the air conditioner runs in a mode other than heating (automatic heating) or it is OFF,
Relay 2 (humidifier) turns off
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above
SW502-1: OFF
• When the air conditioner runs in the heating (automatic heating) mode and room temperature becomes
the set temperature - 2.5 °C (4.5 °F) or lower, Relay 1 (heater) turns on.
When the air conditioner runs in a mode other than the heating (automatic heating) or it is OFF, or then
room temperature becomes the set temperature or higher, Relay 1 (heater) turns off
• When the air conditioner runs in the heating (automatic heating) mode, Relay 2 (humidifier) turns on.
When the air conditioner runs in a mode other than heating (automatic heating) or OFF,
Relay 2 (humidifier) turns off
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above
Relay 1 is on when ON is set by System controller, ME remot controller or MA remote controller,
and off when OFF is set by these controllers. Whwn room temperature becomes the set temperature
or lower in the heating (automatic heating) mode, the Relay 2 (heater) turns on.
When a mode other than heating (automatic heating) or OFF is set by System controller, ME remote
controller or MA remote controller, or when room temperature becomes higher than the set temperature
+1 °C (2 °F), the Relay 2 (heater) turns off.
* This function is to run the heater instead of the air conditioner in the heating mode. The air conditioner
stops in the heating mode. Do not use the remote controller attached to the air conditioner. If you use it,
the operation may not reflect the setting. The position of detecting the room temperature is where MA
remote controller is put, so make sure to connect it to the interface unit.
Relay 1,2:
(coil rating of 12V DC, 1,0
W or less.)
Please use relays with
reinforced insulation
R1
-
+
R2
-
+
Operating details