Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 771

Table of Contents

Advertisement

¢ Forced thermostat off function
NOTE: When the signal is received from another unit on the refrigerant circuit, there may be a de-
lay in thermostat off function at the unit.
• Edge input only
Function setting
60-00
60-02
60-05
60-06
60-07
Example of cooling mode:
Ch3 Input of
CNA03 or CNA04
Thermostat
Room temp.
Set temp.
 Forced thermostat off examples
• Example 1:
– In-line connection
– Function setting for Fan setting when cooling thermostat off
Number 49-00 (Follow the setting on the remote controller)
Forced thermostat off is one of the energy-saving functions. For example, when the outdoor tem-
perature is lower than the indoor temperature, indoor unit of air conditioner perform Fan operation
based on the received signal from external controller. (Cooling only)
Cooling operation
(Thermostat on)
3-2. External input
Connector
Channel no.
CNA03 or CNA04
(EXT. IN2)
On
Off
On
Off
External controller
Thermistor
Damper
Thermistor
Indoor
Outdoor
temperature
temperature
88˚F
82˚F
(31˚C)
(28˚C)
- (08-17) -
Input signal
Off → On
Ch3
On → Off
Fan operation
(Thermostat off)
Command
Thermostat off
Normal
Thermistor
Thermistor
Indoor
Outdoor
temperature
temperature
75˚C
82˚F
(24˚C)
(28˚C)
3. Indoor unit