"Run-mode" - Boot CE, normal operation.
0010
System Restore, resets the file system and registry, reinstalls the system pro-
gram (OPsys_bxxx.CAB). Restores the operator panel to factory settings.
Warning! Information can easily accidently be lost.
0100
Image Load mode (Sysload) allows upgrading of the firmware in the operator
panel.
Note: All files including the file system in the operator panel will be deleted
when upgrading with Image Loader.
1000
Service Menu mode, the service menu for the system program is shown.
Allows the user to set IP configuration, erase the project, calibrate the touch
screen, set the panel in Run/Transfer mode etc. See section
Menu
for details.
1100
Not used (Run-mode).
1110
Self-Test.
xxx1
Hard reset (forces the system to reset).
To change mode switches, follow the steps below:
1. Disconnect power from the operator panel.
2. Set the mode switches using a ballpoint pen.
3. Reconnect power to the operator panel.
3.7.2

Cables

Most of the operator panels use the same type of flex cable connectors.
Flex cable connector
To release the flex cables from the connector, gently push the two flanges on the cable
connector towards the flex cable.
Note:
The connectors must be unlocked on both sides before removing the cable, otherwise
the flex cable may be damaged.