9
Commissioning
9.1
Power-On
Download the Service Expert app from Huawei app store and runs on Android. Apply for
permission after downloading the app.
Ensure that no combustion-supporting materials (air or additives) enter the air
conditioning system during commissioning. Huawei shall not be liable for any risks and
losses thus incurred.
Users are classified into admin and operator. The preset password is 000001 for both
types of users.
After powering on, the smart cooling product is in shutdown mode.
After powering on, the compressor starts preheating, and the system generates an alarm
indicating that the compressor is preheating (for 12 hours). Do not start the smart
cooling product before the preheating ends. Choose Running > Device Details >
Compressor to query the remaining preheating time.
1. Switch on the smart cooling product switch in the upstream power distribution cabinet
(PDC).
2. Turn on the main switches.
3. After the device is powered on for the first time, the LCD displays the Quick Settings screen.
Set parameters as instructed, such as language, date format, date, time, and time zone. If
the device is not powered on for the first time, the home screen is displayed.