Modbus Module - Toshiba TMC7 Series Product Manual

Table of Contents

Advertisement

5.3

MODBUS Module

The MODBUS Module can be used with the TMC7 to enable control and monitoring via a MODBUS RTU network.
Adjustment
Register
Address
Function
40002
Command
40003
Starter Status
40004
Trip Code
40005
Current
40006
Temp
MODBUS Hex Functions
Two functions are supported:
The TMC7 does not accept broadcast functions.
NOTE:
Command, Starter Status, Trip Code, Current and Temperature must be sent individually.
ie one data word request at a time.
Page 17
710-02887-00A
Part Number: TMC7-MBM-01
Type
Write
Read
Read
Read
Read
03 (Multiple read)
06 (Single write)
AP
ASCII
RTU
Protocol
OFF
ON
Example: Address = 24
+16
0
+16
+8
0
+8
Address
+4
0
+4
+2
0
+2
+1
0
+1
ON
ON
4800
9600
19200
Baud Rate
OFF
OFF
ON
OFF
ON
OFF
No Parity
ODD
EVEN
Parity
OFF
OFF
ON
OFF
ON
OFF
No Time Out
10 s
60 s
Time Out
OFF
OFF
ON
(seconds)
OFF
ON
OFF
Description
1=Start
2=Stop
3=Reset
4=Quick Stop
5=Forced Comms Trip
Bit
Description
0-3
0=Not used
1=Ready
2=Starting
3=Running
4=Stopping
6=Tripped
4
1=Forward Phase Rotation
5
Unallocated
6
Unallocated
7
Unallocated
255=No Trip
1=Excess start time
2=Motor overload
3=Motor thermistor
4=Current imbalance
5=Supply frequency
6=Phase rotation
8=Power circuit
16=Comms failure
ACCESSORIES
0
0
0
0
0
38400
ON
ON
10 bit
ON
ON
100 s
ON
ON
TMC7 Series