No.F002 Fire Extinguishing System Conceptual Diagram (CE) - 1
-
+
E
+
Technical requirements:
1. All fire extinguishing signal cables are red (BOM number: 25030029) and black (BOM number: 25030073) cables with naked crimping single-wire cord end terminals (BOM number: 14170214). The red cable is positive and the black
cable is negative. The pneumatic switch, Warning signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the diagram.
2. Connect a 10K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
3. Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
4. Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial.
5. Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT RELAY. The signal cables connect
contacts.
6. Attach cable labels to all cables connected to the extinguishant control panel, wiring terminals on electrical actuators, wiring terminals on pneumatic switches, and cables reserved for combined pre-fab. modules . See the label table for
the label content. Cable direction labels must be arranged neatly in the same direction. Cables must be bound neatly, with cable ties in the same direction. (Labels are printed on label paper with the BOM number 29041061, attached on
cable ties with the BOM number 21200708, and bound to corresponding cables.)
Terminal Resistor
Terminal Resistor
6.8K
6.8K
S
Terminal Resistor
10K
Fire Alarm Bell-1
1
2
3
4
3
B
B
Z
Z
Z
1
1
2
10K
red
black
red
black red
+
-
+
-
+
-
+
-
+
-
+
ROV
SIL
AL
FLT RST
AUX
S1
S2
ZONE 1
ZONE 2
REMOTE
DATA
POWER
CONTROL
STATUS UNITS
Data cable
Power cable Connect the
Connect smoke
Connect heat
first stage
detector in
detector in
alarm to the
detection zone 1
detection zone 2
fire alarm
bell.
Warning Signs-1
I/P
COMM+LEV1 LEV2
2WIRE
SILENCE
COMM+ LEV1 LEV2
S
Extinguishant Abort Button-1
2
4
6.8K
1
3
470Ω
3
4
4
2
2
1
Z
N
N
2
D
D
H
S
S
6.8K
6.8K
6.8K
black
red
red
black
+
-
+
-
+
-
+
-
+
-
NC
C
NO
NC
C
NO
ZONE 3
2ND
1ST
2ND
MODE
MAN
HOLD
SOUNDER
STAGE
STAGE
SELECT
RELEASE
Connect the second
Connect the
stage alarm to the
emergency
horn strobes and
abort port to the
warning signs .
extinguishant
abort button .
Horn Strobes-2
Horn Strobes-1
Terminal Resistor
10K
- + +
- + +
I/P
2WIRE
SILENCE
Pneumatic switch-1
6.8K
13
14
21
22
To Monitoring system
Electrical Actuator-1
1
2
4
1
2
1
2
green
brown
green
brown
green
H
& white
& white
P
P
S
S
6.8K
black
red
black
red
black
-
+
-
+
-
+
-
NO
C
NC
C
NC
C
NO NC
C
NO
REL
EXTING
LOW
EXTRACT
FAULT
LOCAL
PRESS
PRESS
RELAY
FIRE
SWITCH
SWITCH
Connect the
Connect the
Connect the fault
Connect the gas
Connect the fire
pressure signal
electrical actuator
signal output (NO)
release signal
alarm signal output
to the
drive signal to the
to the collector of
output (NO) to the
(NO) to the
pneumatic
electrical actuator.
the monitoring
collector of the
collector of the
switch.
system.
monitoring system.
monitoring system.
brown
& white
NO
FIRE
RELAY