Component
Category
System
Configuration
Configuration attributes
Device
Voltage Thresholds
Configuration
Device
Voltage Hysteresis
Configuration
Main PDF-1
ABB 8D ATS Initial Configuration Parameters
Parameter
Password
Rated Voltage
Rated Frequency
Number of Phases LN1
Number of Phases LN2
Secondary Load
Generator Usage
Line priority
Volt Threshold Min LN1
Volt Threshold Min LN2
Volt Threshold Max LN1
Volt Threshold Max LN2
Volt Hysteresis Min LN1
Volt Hysteresis Min LN2
Volt Hysteresis Max LN1
Volt Hysteresis Max LN2
Default Value
0001
100/57 V-115/66 V-120/70 V-208/120 V-220/127 V-230/132
400/230 V
V-240/138 V-277/160 V-347/200 V-380/220 V-400/230 V-
415/240 V-440/254 V-480/277 V
50 Hz
3 phases with N
3 phases with N/3 phases without N/1 phase
3 phases with N
3 phases with N/3 phases without N/1 phase
Not Used
Not Used/Opening Only/Opening And Closing
No Generator
No Generator, Generator In Use
Line 1–Switch I
Line 1 – Switch I/Line 2 – Switch II/No Line Priority
-20%
-20%
+20%
+20%
-8%
-8%
+8%
+8%
Value Range
/
50 Hz, 60 Hz
-30% to -5%
-30% to -5%
+5% to +30%
+5% to +30%
-29% to -4%, step 1%
-29% to -4%, step 1%
+4% to +29%, step 1%
+4% to +29%, step 1%
Setting
Remarks
Default value
N/A
415/240 V
N/A
50 Hz
N/A
3 phases with N
N/A
3 phases with N
N/A
Default Value
N/A
Generator In Use
N/A
Line 1 – Switch
N/A
-10%
N/A
-10%
N/A
+10%
N/A
+10%
N/A
N/A
-8%
N/A
-8%
N/A
+8%
N/A
+8%

Advertisement