9. Connect the power supply to Magne. The programming of the new Eva is completed
when the LED on Magne illuminates solid green.
Erase code in Magne 4 OSSD
1.
Move the old Eva out of sensing distance from Adam.
2.
Disconnect the power supply from Magne (0 V should always be connected).
3.
Connect +24 VDC to OSSD1 Out and OSSD2 Out.
4. Connect the power supply to Magne (marked +24 VDC).
5.
Disconnect the power supply from both OSSD1 out and OSSD2 out after 5 seconds
and within 10 seconds. The Adam unit in Magne is now reset and the LED on Magne
should flash red.
6. Disconnect the power supply from Magne (marked +24 VDC).
7.
Remove the old Eva.
8. Install the new Eva and move it within sensing distance to Adam.
9. Connect the power supply to Magne. The programming of the new Eva is completed
when the LED on Magne illuminates solid green.