11.
In "Remote Device Initial Setting Procedure Registration" window, right-click the icon and click "Hexadecimal" of the
"Input Format". Set the items in the initial settings as follows.
• Initial setting for an AJ65VBTCU-68ADVN (station No.1)
Setting the initial setting executes the following processing from the first condition.
Condition
Description
1st
The CH.1 and CH.2 are set to the A/D conversion enable.
2nd
An input range is set.
• CH.1: 0 to 5V
• CH.2: User range setting 1 (-10 to 10V)
3rd
Whether a averaging processing or averaging process is executed is set.
• CH.1: Sampling processing
• CH.2: Averaging processing (count average)
4th
The average count of the CH.2 is set to 16.
5th
Initial data processing completion flag is turned on.
6th
Initial data setting request flag is turned on.
7th
Initial data processing completion flag is turned off.
8th
Initial data setting request flag is turned off.