A5D2/A5D3 Demand/Peak Demand Fast Meter Message; A5B9 Fast Meter Status Acknowledge Message; A5Ce Fast Operate Configuration Block - Schweitzer Engineering Laboratories SEL-351 Instruction Manual

Directional overcurrent relay reclosing relay fault locator
Table of Contents

Advertisement

02
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
51332D000000 Analog channel name (Q3-)
02
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
00
Reserved
checksum

A5D2/A5D3 Demand/Peak Demand Fast Meter Message

In response to the A5D2 or A5D3 request, the relay sends the following block:
A5D2 or A5D3 Command
BE
1-byte
176-bytes
8-bytes
1-byte
1-byte

A5B9 Fast Meter Status Acknowledge Message

In response to the A5B9 request, the relay clears the Fast Meter (message A5D1) Status Byte. The
SEL-351 Status Byte contains one active bit, STSET (bit 4). The bit is set on power up and on
settings changes. If the STSET bit is set, the external device should request the A5C1, A5C2, and
A5C3 messages. The external device can then determine if the scale factors or line configuration
parameters have been modified.

A5CE Fast Operate Configuration Block

In response to the A5CE request, the relay sends the following block:
Data
A5CE
24
01
0008
0100
31
11
00
20
40
01
21
Date Code 20001006
Courtesy of NationalSwitchgear.com
1-byte checksum of preceding bytes
Length
1 Status Byte
Demand: IA, IB, IC, IN, IG, 3I2, MWA I, MWB I, MWC I, MW3PI,
MVA I, MVB I, MVC I, MV3PI, MWA O, MWB O, MWC O,
MW3PO, MVA O, MVB O, MVC O, MV3PO in 8-byte IEEE FPS
Time stamp
Reserved
1-byte checksum of all preceding bytes
Description
Command
Length
Support 1 circuit breaker
Support 8 remote bit set/clear commands
Allow remote bit pulse commands
Operate code, open breaker 1
Operate code, close breaker 1
Operate code, clear remote bit RB1
Operate code, set remote bit RB1
Operate code, pulse remote bit RB1
Operate code, clear remote bit RB2
Operate code, set remote bit RB2
Configuration, Fast Meter, and Fast Operate Commands
SEL-351 Instruction Manual
D-9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SEL-351 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF