Application; General; Proper Use; Safety And Precautions - ABB EAN823 Instructions Manual

Power electronic units for field installation. for the control of contrac actuators of the pme, lme, rhd or rsd series
Hide thumbs Also See for EAN823:
Table of Contents

Advertisement

2.

Application

Use this instruction only together with the actuator instruction.
3.

General

3.1

Proper Use

Power electronics models EAN823, EBN853 and EBN861 are to be used exlusively for triggering elek-
trical actuators of the PME120, LME 620, RSD... or RHD... series. Do not use them for any other pur-
pose. Otherwise, a hazard of personal injury or of damage to or impairment of the operational reliability
of the device may arise.
3.2

Safety and Precautions

When mounting the electronics in areas which may be accessed by unauthorized persons, take the re-
quired protective measures.
- Only qualified specialists who have been trained for these tasks are authorized to mount and adjust
the electronics, and to make the electrical connection.
- When working on the electronics always observe the locally valid accident prevention regulations
and the regulations concerning the construction of technical installations.
- Switch-off the voltage supply; make sure that unintentional switching on is not possible
- Make sure that cutting off the voltage supply does not affect the plant process
- Consider restoring process forces from the final control element when cutting off the voltage
4.

Storage

The devices may be stored under moist and aggressive condition for a short time. The equipment is
protected against external corrosive influences. However, direct exposure to rain, snow, etc. must be
avoided
Condensation may occur in the terminal box. Therefore, it is protected by a desiccant, which ensures
sufficient protection for approximately 150 days. The desiccant can be regenerated at a temperature of
90° C within 4 h.
The desiccant must be removed prior to commissioning the electronics.
4.1

Long-time Storage

If you intend to store or transport the device for a longer time, we recommend to wrap it in plastic foil
and add desiccant. Regularly check if the desiccant is still active.
5.

Delivery settings

Behavior in 0/100% position:
Setpoint function:
Input (setpoint):
Function:
Output (actual value):
1)
Digital inputs:
1)
Digital outputs:
Range:
The configuration of your actuator may differ from the standard configuration specified above. It can be
called up for display using a notebook / PC and the related configuration program.
1)
not with fieldbus communication.
Keep closed with rated torque
Linear; setpoint = positioning value
1)
4 ... 20 mA
Positioner, parameter: setpoint
1)
4 ... 20 mA
DI 1 switch-over manual/automatic and v.v.
DI 2 / DI 3 manual control +/-
DO 1 ready to operate, DO 2/3 end position signalling
Not adjusted (to be adjusted during commissioning)
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebn853Ebn861

Table of Contents