Cabinet Modules
6.3 Motor Modules
6.3.5

Overload capability

The Motor Modules Chassis format have an overload reserve (e.g. to handle breakaway
torques).
In drives with overload requirements, the appropriate base-load current must therefore be
used as a basis for the required load.
For overload, the following precondition applies: The drive is operated as a maximum with its
base load current before and after the overload occurs (a duty cycle duration of 300 s is
used as a basis here).
Another precondition is that the drive is operated with its factory-set pulse frequency at
output frequencies >10 Hz.
For additional information on the overload capability, see the Low Voltage Configuration
Manual and in the SINAMICS S 120 Function Manual Drive Functions.
Low overload
The base load current I
duty cycle of 300 s.
Figure 6-18
202
is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a