6.4

Offline auto tuning

• The offline auto tuning enables the optimal operation of a motor with encoder.
Pr.
Name
96
Auto tuning setting/status
C110
463
Second motor auto tuning setting/status
C210
POINT
POINT
• Refer to the Instruction Manual (Detailed) of the inverter to perform the offline auto tuning.
• This section explains the specific information of the motor with an encoder.
Vector
Vector
Vector
Initial
Setting
value
range
0
No offline auto tuning
1
Performs offline auto tuning (without motor rotation)
Performs offline auto tuning only for motor constant R1 (without
11
0
motor rotation)
Performs encoder position tuning
101
and offline auto tuning
(with motor slight rotation)
Performs offline auto tuning for the second motor (Refer to Pr.96 for
0
0, 1, 11, 101
the setting.)
Description
PM motor
Induction motor
Performs offline auto tuning
(with motor rotation)