(1) Strip off the sheath of the signal cable from the encoder for the below length. If the length of the sheath peeled is too long,
a short circuit may occur with neighboring wires. If the length is too short, wires might come off.
Wire the stripped signal cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Cable stripping length
For connecting the FR-A8APS, use a blade terminal as necessary.
When using the blade terminal, use care so that the twisted wires do not come out.
NOTE
• Blade terminals commercially available (as of February 2016. The product may be changed without notice.)
Terminal
Wire size (mm
screw size
M2
0.3 to 0.5
12
INSTALLATION AND WIRING
5 mm
Damaged
Ferrule terminal model
2
)
With insulation sleeve
Al 0,5-6WH
Unstranded
wires
Wires are not inserted
Crumpled tip
into the sleeve
Without insulation sleeve
A 0,5-6
Crimping tool
Manufacturer
name
Phoenix Contact
CRIMPFOX 6
Co., Ltd.