Mitsubishi Electric 800 Series Function Manual page 43

Cc-link ie tsn communication function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Programming example for fault record reading
The following program reads fault records of station 1 inverter to D1.
• Fault history No. 1, No. 2 reading instruction code: H74 (hexadecimal)
For the error code, refer to the Instruction Manual (Detailed) of the inverter.
The reply code at the time of instruction code execution is set to D2. (RWr10: Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302 X1025
16
24
 Programming example for resetting the inverter at inverter error
The following is a program example for resetting station 1 inverter at inverter error.
SB49
SW0B0.0
0
M0 X103A X20
3
Error status flag
7
NOTE
• The above inverter reset using RY3A may be made only when an inverter error occurs.
When Pr.349 Communication reset selection/Ready bit status selection/Reset selection when inverter errors cleared
is set to "0, 100, 1000, or 1100", inverter reset is available in any operation mode.
• When using the instruction code execution request (RY25) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in Pr.340 Communication startup mode selection or change the operation mode to the
Network operation mode. (For the program example, refer to
(N) Operation via communication and its settings
M0
Check the data link status of the station 1
PLS M300
SET M301
Write fault history No.1 and No.2 read
MOV H74
W110
code (H74) to RWw10.
SET Y1025
Turn on the instruction code execution request
(RY25)
RST M301
SET M302
MOV W11 D1
Read fault record (RWr11) and reply code
(RWr10) to D1 and D2 when the instruction
MOV W10 D2
code execution completion (RX25) turns on.
Turn off the instruction code execution request
RST Y1025
(RY25)
RST M302
END
M0
Check the data link status of the station 1
Turn on the error reset request flag (RY3A)
Y103A
Turn off the error reset request flag (RY3A)
when the error status flag (RX3A) is off.
END
page
39)
page
33)
PARAMETER
2
GROUP
N
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

A800-gn