7.1.2 Starting the Inverter

Starting the Inverter on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 On the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End
Starting the Inverter on the WebUI
Step 1 Open a browser (Internet Explorer 11 as an example) and choose Tools > Internet
Options.
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and
click OK.
Figure 7-2 Setting Internet options
Step 3 In the address box of the browser, enter https://
Step 4 Enter the correct user name and password and click Login.
Step 5 To ensure system security, change the preset password after login.
Step 6 On the WebUI, choose Monitoring > UPS System > Running Control, and click
Inv. ON, and confirm the operation to start the inverter.
Issue 01 (2020-11-30)
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.