Huawei UPS5000-H Series User Manual page 60

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Item
Bypass input
Output
Battery
input (lead-
acid
battery)
Battery
input
(SmartLi)
Issue 01 (2020-11-30)
Bypass input current
(A)
Recommende
d cross-
sectional area
2
(mm
)
Output current (A)
Recommende
d cross-
sectional area
2
(mm
)
Nominal battery
discharge current
(A)
Maximum battery
discharge current
(A)
Recommende
d cross-
sectional area
2
(mm
)
Nominal battery
discharge current
(A)
Maximum battery
discharge current
(A)
Recommended
cross-sectional area
2
(mm
)
Copyright © Huawei Technologies Co., Ltd.
400 kVA
N
PE
2×120
608
L1
2 x (4 x
240)
L2
L3
N
PE
2×120
608
U
2 x (4 x
240)
V
W
N
PE
2×120
887
1062
+
2 x (2 x
240)
-
PE
240
822
1032
For details, see the IEC 60364-5-52
specifications and SmartLi user manual.
6 Installation
500 kVA
600 kVA
3×120
4×95
760
912
2 x (4 x
3 x (4 x
240)
240)
2×120
3×120
760
912
2 x (4 x
3 x (4 x
240)
240)
2×120
3×120
1108
1330
1327
1593
3 x (2 x
3 x (2 x
185)
240)
240
240
1028
1234
1290
1547
53