Alarm ID
Alarm
Name
2065
Upgrade
Failed
2066
License
Expired
61440
Monitorin
g Unit
Faulty
2067
Faulty
Power
Collector
2072
Transient
AC
Overvolta
ge
Issue 02 (2019-04-30)
Alarm
Possible Cause
Severity
Major
The upgrade does not end
normally.
Minor
The privilege certificate has
entered the grace period.
The privilege feature will
be invalid soon.
1. The flash memory is
Minor
insufficient.
2. The flash memory has bad
sectors.
Major
In grid connection with
zero power mode, the
power meter
communication is
interrupted.
In grid connection with
Grid connected with zero
power, the power meter
communication is
interrupted.
Major
The inverter detects that the
phase voltage exceeds the
transient AC overvoltage
protection threshold.
Copyright © Huawei Technologies Co., Ltd.
SUN2000-(3KTL-10KTL)
Troubleshooting Suggestion
1. Perform the upgrade again.
2. If the upgrade fails several times,
contact your dealer or Huawei
technical support.
1. Apply for a new certificate.
2. Load the new certificate.
Turn off the AC output switch and
then the DC input switch. After 5
minutes, turn on the AC output
switch and then the DC input switch.
If the fault persists, replace the
board, If the upgrade fails several
times, contact your dealer or Huawei
technical support.
1. Check that the power meter
settings are based on the actual
model.
2. Check that the communications
parameters for the power meter
are the same as the SUN2000
RS485 parameter settings.
3. Check that the power meter is
powered on, and the RS485 cable
is connected correctly.
1. Check whether the grid
connection voltage exceeds the
upper threshold. If yes, contact
the local power operator.
2. If you have confirmed that the
grid-tied voltage exceeds the
upper threshold and have
obtained the consent of the local
power operator, modify the
overvoltage protection threshold
through the mobile phone app,
SmartLogger, or NMS.
3. Check whether the peak power
grid voltage exceeds the upper
threshold.
User Manual
Page 66 of 81