Huawei SUN2000 Series User Manual page 36

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

No.
E
F
G
Table 5-2 Cable description
No.
1
2
3
Issue 02 (2019-04-30)
Component
Description
Electricity
The recommended electricity meter
meter
model is DTSU666-H.
Power grid
Choose a device that meets
scheduling
requirements of power grid
device
scheduling.
AC switch
Recommended: a three-phase AC
circuit breaker with a rated voltage
greater than or equal to 380 V AC
and a rated current of:
Name
DC input power cable
(Optional) RS485
communications cable
(used to cascade inverters
or connect to the RS485
signal port on the
SmartLogger)
(Optional) RS485
communications cable
(used to connect to the
RS485 signal port on
devices such as the Smart
Power Sensor and the
energy storage device)
Copyright © Huawei Technologies Co., Ltd.
16 A (SUN2000-3KTL-M0,
SUN2000-4KTL-M0,
SUN2000-5KTL-M0,
SUN2000-6KTL-M0)
25 A (SUN2000-8KTL-M0,
SUN2000-10KTL-M0)
Type
Standard PV cable in the
industry
Two-core outdoor
shielded twisted pair
cable
Two-core outdoor
shielded twisted pair
cable
SUN2000-(3KTL-10KTL)
User Manual
Source
Purchased from
Huawei
Provided by local
power grid
companies
Prepared by the
customer
Specifications
Conductor
cross-sectional area:
2
4–6 mm
Cable outer diameter:
4.5–7.8 mm
Conductor
cross-sectional area:
2
0.2–1 mm
Cable outer diameter:
4–11 mm
Conductor
cross-sectional area:
2
0.2–1 mm
Note: When devices
such as the Smart
Power Sensor and the
energy storage device
are both connected to
the inverter, use
2
0.2–0.5 mm
cords.
Cable outer diameter:
4–11 mm
Page 36 of 81

Advertisement

Table of Contents
loading

Table of Contents