Introduction; Minimum Requirements; Ac Mains - Wire Gauge; Grounding - Hitachi E-Compact Medium Power Series Operation Manual

Uhf digital tv transmitters
Table of Contents

Advertisement

1. Introduction.

This section provides information on the minimum installation requirements for E-Compact
Series transmitters with recommendations on shelter, tower, antennas, cables, grounding,
mains, transient preventions, etc.

2. Minimum Requirements.

2.1. AC Mains - Wire Gauge.

Consumption with the equipment running at its maximum power.
Current (A) on each wire:
About AC MAINS TYPE, see Section 8 – Attachments, USA AC Mains Types for E-
Compact Series.
MODELO
Typical
EC702MP
EC704MP
Not available or uncommon use
The current quoted in the table is more loaded phase to sizing effect of conductors and
protection.
Said gauge is the minimum recommended for the transmitter in question, if the cable
length is large, consider voltage drop in the cable maximum of 5%
The section of the neutral conductor should be the same as the phase.
The section of the ground conductor has to be the same as the conductors phase.

2.2. Grounding.

The grounding system to which the Hitachi Kokusai Linear TV transmitter will be attached
must be designed and implemented by a qualified professional. An improper grounding
system may jeopardize the equipment as well as the lives-of the professionals working in
the shelter. To be considered proper, the grounding must have a resistance of no more than
5 Ohms.
E-Compact Series - ATSC
M120
Wire diameter
(A)
(A)
mm²
AWG
Typical
6,3
4,17
11
3,6
7,2
M208 / B240
T208 / T240
Wire diameter
(A)
mm²
AWG
Typical
3,31
12
4,17
11
E-Compact Medium Power
T380
Wire diameter
Wire diameter
(A)
mm²
AWG
Typical
mm²
AWG
14 | 106