Group transient transmission

This function This function sends data to all stations of the same transient transmission group number by dividing the transient
transmission target stations into groups.
One network can be divided into a maximum of 32 groups.
Setting the group specification for the target station number of the control data of the link dedicated instruction allows
capturing of transient data at the station where the group number matches.
Executing instructions by setting No.1 for group specification from station No.2 allows capturing of transient data at three
stations: station No.3, station No.4, and station No.5.
(1)
(2)
(4)
(5)
Group No.1
(1) Control station (station No.1)
(2) Normal station (station No.2)
(3) Normal station (station No.3)
(4) Normal station (station No.4)
(5) Normal station (station No.5)
(6) Normal station (station No.6)
Setting method
For the setting method, refer to the following.
Page 72 Transient Transmission Group No.
Dedicated Instruction
The following describes the dedicated instructions for which group numbers can be specified.
 MELSEC iQ-R Programming Manual (Module Dedicated Instructions)
Instruction
WRITE
SWRITE
SEND
REQ
ZNWR
RRUN
RSTOP
RTMWR
Precautions
• The execution cannot be checked with the transient transmission by group specification.
• If executed transient transmission continuously, transient transmission cannot be performed because of too much
processing of transient transmission (link dedicated instruction). Continuous execution may cause an error (Error code:
1845H). Therefore, perform debugging after ensuring that the execution interval is set in the system and check that
continuous execution can be performed.
Group No.1
(3)
Network No.1
(6)
Group No.1
Description
Writes data in the word device of another station.
Writes data in the word device of another station. (With completion device)
Sends data to another station.
Requests the remote RUN/STOP to the CPU module on another station.
Reads/writes clock data from/to another station.
Writes data in the word device of another station. (For MELSEC-A series)
Sends the request of remote RUN to another station.
Sends the request of remote STOP to another station.
Writes the clock data to another station.
1 FUNCTIONS
1.2 Transient Transmission Function
1
37