Running The Motor In Jog Mode (Jog Function) - Siemens SINAMICS G120 CU230P-2 HVAC Operating Instructions Manual

Frequency converters with the control units
Hide thumbs Also See for SINAMICS G120 CU230P-2 HVAC:
Table of Contents

Advertisement

Functions
7.4 Setpoint sources
Example: Selecting two fixed speed setpoints using digital input 2 and digital input 3
The motor is to run at two different speeds:
● The motor is switched on with digital input 0
● When digital input 2 is selected, the motor is to run at a speed of 300 rpm.
● When digital input 3 is selected, the motor is to accelerate to a speed of 2000 rpm.
● When digital input 1 is selected, the motor should go into reverse
Table 7- 21
Parameter
p0015 = 12
p1001 = 300.000
p1002 = 2000.000
p1016 = 1
p1020 = 722.2
p1021 = 722.3
p1070 = 1024
7.4.4

Running the motor in jog mode (JOG function)

Using the "jog" function (JOG function), you can switch the motor on and off using a control
command or the operator panel. The speed to which the motor accelerates for "Jog" can be
set.
The motor must be switched-off before you issue the "jog" control command. "Jog" has no
effect when the motor is switched on.
The "Jog" function is typically used to manually switch-on a motor after switching over from
automatic to manual operation.
Setting jogging
The "Jog" function has two different speed setpoints, e.g. for motor counter-clockwise
rotation and clockwise rotation.
With an operator panel, you can always select the "Jog" function. If you wish to use
additional digital inputs as control commands, you must interconnect the particular signal
source with a digital input.
200
Parameter settings for the example
Description
Macro drive unit: Configure inverter with terminal strip as the command
and setpoint source.
The motor is switched on and off via digital input 0.
The setpoint source is analog input 0.
Defines the fixed setpoint 1 in [rpm]
Defines the fixed setpoint 2 in [rpm]
Direct selection of fixed setpoints
Interconnection of fixed setpoint 2 with DI 2.
r0722.2 = parameter that displays the status of digital input 2.
Interconnection of fixed setpoint 3 with status of DI 3.
r0722.3 = parameter that displays the status of digital input 3.
Interconnect main setpoint with fixed speed setpoint
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD