3.3
Logging In to the UPS WebUI and Setting Parameters
1. Use a straight-through cable to connect the PC to
the FE port on the UPS MDU.
2. Enter https://UPS IP address in the address box
of Internet Explorer to log in to the UPS WebUI
homepage.
NOTE
Default UPS settings:
IP address: 192.168.0.10
Subnet mask: 255.255.255.0
Gateway: 192.168.0.1
3. On the UPS WebUI homepage, choose Param. Settings > Battery Setting, and set Number of
battery strings.
4. On the UPS WebUI homepage, choose iBOX Settings, and set Basic Param., Advanced
Param., and Batt. String Config.
NOTE
If the BCB box is configured, set Batt. abnormal BCB trip to Enable.
User Name: admin
Password: Changeme