General Installation Environments; Industrial Environment Installations; Hardware Installation; Mounting The Energy Pack On A Din Rail - GE PACSystems IC695CPU3104 Manual

Programmable control products, battery and energy pack
Table of Contents

Advertisement

Energy Packs
3.2.2

General Installation Environments

In order to maintain the Agency Certifications listed below, installation must comply with the following
requirements.
The Energy Pack
The Energy Pack must be installed in a Pollution Degree 2 environment as defined by:
 Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become
conductive due to occasional condensation.
3.2.3

Industrial Environment Installations

For use in industrial environments this product is considered open equipment [having live electrical parts that may
be accessible to users] and must be installed in an ultimate enclosure that is manufactured to provide safety. At a
minimum, the enclosure shall provide a degree of protection against solid objects up to 12mm (0.5") (e.g. fingers).
This equates to a NEMA/UL Type 1 enclosure or an IP20 rating (IEC60529) providing at least a pollution degree 2
environment.
3.2.4

Hardware Installation

The Energy Pack can be mounted on a standard EN50022 DIN rail or an equipment panel. It is designed to be
mounted adjacent to the Controller and connected to the Controller using the provided 12" (0.3m) cable
(ICRXIACCCBL01A) or a user-supplied cable.
Refer to section on Grounding for important grounding instructions.
3.2.4.1

Mounting the Energy Pack on a DIN Rail

The Energy Pack snaps easily onto the DIN rail. No tools are required.
Note: To remove the Energy Pack from the DIN rail, use a small flat-blade screwdriver to pull down on the tab on
the bottom of the Energy Pack and then lift the module off the DIN rail.
18
must be installed in
 Access can only be gained by service persons or by users who have been instructed
about the reasons for the restrictions applied to the location and about any
precautions that shall be taken; and
 Access is through the use of a tool or lock and key, or other means of security, and
is controlled by the authority responsible for the location.
PACSystems* Controllers Battery and Energy Pack Manual
Warning
a Restricted Access Area, as defined by:
GFK-2741D