Download Print this page

Hitachi Hidic EH-150 Applications Manual page 91

Ethernet module
Hide thumbs Also See for Hidic EH-150:

Advertisement

Preliminary Rev.03
9.3.2
How to turn off LED
ERR LED and I.ERR LED can be confirmed light/unlighted status or made turned off by ladder program.
(1) Confirm LED light
Ladder program can confirm the status(light or unlighted) of ERR and I.ERR.
The status of each LED is stored in module status register(MDSR) in EH-ETH.
Module status register (MDSR)
Bit
15 to 8
+00
You can read the value of MDSR to WM10 by the below ladder program. As a result, M100 means the status
of ERR LED and M101 means status of I.ERR LED.
R7E3
R100
(2) How to turn off LED
Ladder program can turn off ERR and I.ERR LEDs. To turn each LED off, set module control
register(MDCR).
Module control register (MDCR)
Bit
15 to 8
+00
The contents of this manual might be changed without notice.
7
6
5
4
-
FAE OPM SME EIE AVR ATR IERR ERR
WM003 = H2
WM004 = H2F
ADRIO = (WM005, R100)
ADRIO = (WM006, WM10)
WM007 = 1
R100 = 1
FUN201 (WM000)
7
6
5
4
-
-
-
-
-
0: Turn-off request cancellation
1: Turn off request
Chapter 9 Maintenance, check, error
3
2
1
0
0: unlighted
ERR LED
1: light
I.ERR LED
(00001)
Set FUN201(s) parameter area for SR read
EH-ETH's mounted position (unit 0, slot 0)
Set control bit I/O No. R100
Set head of I/O No. WM10.
Set transmission sizes 1 word.
Set SR read control bit.
R100
(00002)
S
Execute SR read by R100 = 1.
(00003)
Execute FUN201 command for SR read.
3
2
1
0
AEN IAV
EC1 EC0
ERR LED
I.ERR LED
9-3