5.3
Configuration of Ethernet information using Web browser
This module has the Web server and the set up page for several initial configuration value. User can change
initial configuration value using Web browser(*1). The following items can be set by the set up page.
In this section, the procedure for changing the Ethernet information from the factory set value included in this
module is described.
(1) Ethernet Information for this module
IP address of self station,
Configuration of destination for diagnostic,
Configuration of task code port
(2) Information of connection for automatically
sending/receiving operation
(3) Information of I/O area for automatically
sending/receiving operation
(4) Downloading/Uploading of setup file
CAUTION
The Web browser is required having frame function. (Ex. Netscape Navigator Ver2.0 later or Microsoft Internet
Explorer Ver3.0 later)
5.3.1
Access for set us page
(1) Setting the dip switch
To configure the Ethernet information by using Web browser, setting dip switch bit1 is ON and bit 2 is OFF is
required. In this condition, bit3 to 6 setting value of dip switch are used for the lower 6 bits of IP address. And
the rested upper 26bits is fixed value. Therefore, in this mode the IP address can be selected from
"192.168.0.1" to "192.168.0.63".
The method of setting the dip switch is shown in table 5.4. And IP address status in this mode is shown in
figure 5.4
Table 5.4 Setting the dip switch (Configuration Ethernet information by Web browser
1
2
OFF
ON
192.
1 1 0 0 0 0 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 * * * * * *
Figure 5.4 IP address during the configuration of Ethernet information by Web browser
CAUTION
- Because of the IP address of "192.168.0.0" has special meaning, please not to set the dip switch bit 1 is ON and bit 2
is OFF and don't turn bit3 to 8 into OFF. If with this power ON in this condition, STATUS LED will blink 6 times
with red color.
- This dip switch setting is used as temporary setting to access Web server in this module. This dip switch setting is not
saved into retaining memory of this module.
- In case of this module is connected into the exist network system, be careful not to multiple the IP address with the
other equipment.
The contents of this manual might be changed without notice.
Chapter 5 Configuration and procedure for starting communication
Table 5.3 The list of the items can be configured by Web browser
Items
Bit No.
3
4
5
6
7
IP address lower byte
b'000001 to b'111111(1 to 63)
168.
Upper 26 bits (fixed)
Section number to refer
This section
Section 5.3.x
Section 5.3.x
Section 5.3.x
Description
8
To configure the Ethernet Information by Web browser.
0.
5-4
1 to 63
Lower 6 bits