Preliminary Rev.03
Module Control Register (MDCR)
Bit
+0
Bit 15-4: Reserved
These bits are reserved. Please set "0" always.
Bit 3: Automatic Sending/Receiving enable bit (AEN)
To specify whether Automatic Sending/Receiving function is used or not.
Bit3: AEN
0
1
The confirmation of this bit control can be confirmed referring ATR bit of Module Status Register (MDSR) bit2.
Bit 2: Request bit to confirm existence of the module (IAV)
This bit is used when to confirm this module is alive or not. The value specified this bit is reflected to AVR bit of
Module Status Register(MDSR) bit3. If the set value is not reflected to AVR, some problem may be happen in this
module. If this bit programmed to set by user ladder diagram, the value of this bit will not be reflected without
starting run of CPU module.
Bit2: IAV
0
1
Bit 1: I.ERR LED indication/Clear bit (EC1)
This bit is used to turn I.ERR LED off. And also this bit clear IERR bit of Module Status Register bit1.
Bit1: EC1
0
1
Bit 0: ERR LED indication/Clear bit (EC0)
This bit is used to turn ERR LED off. And also this bit clear ERR bit of Module Status Register bit0.
Bit0: EC0
0
1
The contents of this manual might be changed without notice.
15
14
13
12
11
Request to disable Automatic Sending/Receiving function.
Request to enable Automatic Sending/Receiving function.
Request to clear the existence response bit (AVR) of status area.
Request to set the existence response bit (AVR) of status area.
Nothing is done.
Request to turn I.ERR LED off and clear IERR bit to "0".
Nothing to done.
Request to turn ERR LED off and clear ERR bit to "0".
10
9
8
7
6
Description
Description
Description
Description
8-7
Chapter 8 Register Structure
5
4
3
2
1
AEN IAV
EC1 EC0
(Initial set)
(Initial set)
(Initial set)
(Initial set)
0