08/2005
232805
<location>Encoder 2: Incorrect EPROM checksum
Reaction:
A_INFEED: OFF2 (NONE)
SERVO: ENCODER (DCBRAKE, NONE)
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
Replace the module.
232806
<location>Encoder 2: Initialization unsuccessful
Reaction:
A_INFEED: OFF2 (NONE)
SERVO: ENCODER (DCBRAKE, NONE)
Acknowledge:
READY
Cause:
The encoder was not successfully initialized.
Fault value (r0949, hexadecimal):
1, 2, 3: Encode initialization with the motor rotating.
Remedy:
Acknowledge the fault.
232820
<location>Encoder 2 DRIVE-CLiQ: Telegram error
Reaction:
A_INFEED: OFF2
SERVO: ENCODER (DCBRAKE, NONE)
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communications error between the control unit and the encoder involved.
Fault value (r0949, hexadecimal):
01: CRC error.
02: Telegram is shorter than specified in the length byte or in the receive list.
03: Telegram is longer than specified in the length byte or in the receive list.
04: The length of the receive telegram does not match the receive list.
05: The type of the receive telegram does not match the receive list.
06: The address of the encoder in the telegram and in the receive list do not match.
07: The encoder expects a SYNC telegram, but the receive telegram is not a SYNC
telegram.
08: The encoder does not expect a SYNC telegram, but the receive telegram is a SYNC
telegram.
09: The error bit in the receive telegram is set.
10: The receive telegram is too early.
Remedy:
- carry-out a POWER ON.
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916
232835
<location>Encoder 2 DRIVE-CLiQ: Cyclic data transfer error
Reaction:
A_INFEED: OFF2
SERVO: ENCODER (DCBRAKE, NONE)
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communications error between the control unit and the encoder involved. The
nodes do not send and receive in synchronism.
Fault value (r0949, hexadecimal):
21: The cyclic telegram has not been received.
22: Timeout in the telegram receive list.
40: Timeout in the telegram send list.
Remedy:
- carry-out a POWER ON.
- replace the component involved.
See also: p9916
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-761