1MRK 511 244-UUS A
DNP3 device profile document
Pulse off
Never
○
Latch on
Never
○
Latch off
Never
○
Queue
Never
●
Clear queue
Never
●
Explanation of "Sometimes" above: Supported binary output control operations depend on the type of point. Please consult the
binary output point list description.
Reports binary input change events when no specific variation
requested:
Never
○
Only when time-tagged
○
Only non-time-tagged
○
Configurable to send one or the other
●
(Obj2DefVar on DNP3Master)
Sends unsolicited responses:
Never
○
Configurable (UREnable on
●
DNP3Master)
Only certain objects
○
Sometimes (attach explanation)
○
ENABLE/DISABLE UNSOLICITED
●
function codes supported
Default counter object/variation:
No counters reported
○
Configurable (obj20DefVar and
●
obj22DefVar in DNP3Master)
Default object
○
Default variation:
Point-by-point list attached
○
Sends multi-fragment responses:
Yes
○
No
○
Configurable (ApplMultFrgRes on DNP3Master)
●
Deadbanding is not performed in the DNP protocol stack. Any deadbanding is a property of the IED's underlying data and is
configured through the IED configuration tools.
● = Selected,○ = Not selected
DNP, 650 series
Point list manual
Always
○
●
Always
○
●
Always
○
●
Always
○
○
Always
○
○
Reports time-tagged binary input change events when no specific
variation requested:
○
○
○
●
Sends static data in unsolicited responses:
●
○
○
No other options are permitted.
Counters roll over at:
○
○
○
●
○
○
© Copyright 2011 ABB. All rights reserved
Sometimes
Configurable
○
Sometimes
Configurable
○
Sometimes
Configurable
○
Sometimes
Configurable
○
Sometimes
Configurable
○
Never
Binary input change with time
Binary input change with relative time
Configurable (Obj2DefVar on DNP3Master)
Never
When device restarts
When status flags change
No counters reported
Configurable (attach explanation)
16 bits
32 bits
Other value: _______
Point-by-point list attached
Section 3
DNP3 protocol implementation
39