DNP3 data mappings
Function name
SCSWI
SDDRFUF
SDEPSDE
SESRSYN
SLGGIO
SMBRREC
Table continues on next page
28
Signal type
Analog inputs
Binary inputs
Binary outputs
Double bit indications
Binary inputs
Binary inputs
Analog inputs
Binary inputs
Analog inputs
Binary inputs
© Copyright 2011 ABB. All rights reserved
Signal name
SCILO:EN_OPEN
SCSWI:L_CAUSE
SCSWI:CMD_BLK
SCSWI:CLOSE_CMD
SCSWI:OPEN_CMD
SCSWI:POSITION
SDDRFUF:BLKV
SDEPSDE:TRDIRIN
SDEPSDE:.TRIP
SDEPSDE:TRNDIN
SDEPSDE:TRVN
SESRSYN:FRDIFFME
SESRSYN:PHDIFFME
SESRSYN:VDIFFME
SESRSYN:AUTOENOK
SESRSYN:AUTOREL
SESRSYN:B1SEL
SESRSYN:B2SEL
SESRSYN:L2SEL
SESRSYN:LNSEL
SESRSYN:MANENOK
SESRSYN:MANREL
SESRSYN:SYNFAIL
SESRSYN:SYNOK
SESRSYN:SYNPROGR
SLGGIO:SWPOSN
SMBRREC:3PT1
SMBRREC:3PT2
1MRK 511 244-UUS A
Description
Open operation at closed or
intermediate or bad position
is enabled
Latest value of the error
indication during command
Commands are blocked
Close command parameter
for DNP protocol
Open command parameter
for DNP protocol
Position indication
General pickup
Trip of the directional
residual overcurrent
Commontrip signal
Trip of non-directional
residual overcurrent
Trip of non-directional
residual overvoltage
Calculated difference in
frequency
Calculated difference of
phase angle
Calculated difference in
voltage
Automatic energizing check
OK
Automatic release
Bus1 selected
Bus2 selected
Line2 selected
Line selected
Manual energizing check OK
Manual release
Synchronizing failed
Synchronizing failed
Synchronizing OK output
Synchronizing in progress
Switch position as integer
value
Three-phase reclosing in
progress, shot 1
Three-phase reclosing in
progress, shot 2
DNP, 650 series