Appendix F : Default Values Of Parameters - GE Hydran 201i Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

Hydran* 201i Instruction Manual
Table F-1 below presents the default values of the adjustable parameters after the
battery has been disconnected or after the Hydran 201Ti's embedded software has been
upgraded.
Category
Gas level
Hourly Trend
Daily Trend
MA-033
Rev. 14.0, 12-Nov-18

Appendix F : Default Values of Parameters

Parameter
Period B
Low-Low alarm
Low alarm
High Alarm
High-High Alarm
Alarms delay
Trend Period
Low-Low alarm
Low alarm
High Alarm
High-High Alarm
Alarms delay
Trend Period
Low-Low alarm
Low alarm
High Alarm
High-High Alarm
Alarms delay
Unit
Value
Hours
24
ppm
5
ppm
15
ppm
250
ppm
500
Minutes
10
Hours
24
ppm
-20
ppm
-10
ppm
10
ppm
20
% of period 33
Days
30
ppm
-50
ppm
-25
ppm
25
ppm
50
% of period 33
Status
Disabled
Disabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Page 235