WARNING
4. Verify the LED's, the heater, the display and the keypad by performing the
procedure in Section7.2.2.
5. Using the H201Ti's keypad or a host computer running the Hydran Host software
(see the Hydran Host Software Manual), verify the date and time in the Date&Time
submenu (Section 5.5.5) by performing the procedure in Section 7.4.9. If they
must be adjusted, see Section 7.2.3.
6. Verify the four parameters in the History;HistoSetup submenu (Section 5.5.1). If
they must be adjusted, see Section 7.4.2.
7. Verify the parameters in the Gas submenu (Section 5.5.2). If they must be
adjusted, see Section 7.4.3.
8. Verify the parameters in the Temperature submenu (Section 5.5.3). If they must
be adjusted, see Section 7.4.5.
9. Verify the Period A and Period B parameters in the Temperature;DynOil Sampl
submenu.
10. Verify the SerialNumber, the ten H201 sensor parameters and the CheckSum (all
in the Service;SensorCal Data submenu, Section 5.5.4.1) correspond to those
written on the Test Certificate and Data Sheet (see an example in Figure 7-1). If
those parameters must be adjusted, see Section 7.4.6.
11. Verify the parameters (only accessed using the H201Ti's keypad) in the
Communication submenu (Section 5.5.6) by performing the procedure in Section
7.4.10. If they must be adjusted, see Section 7.4.1.
12. Verify the operation mode of the TDM signal in the Relays/Analog;TDM Out
submenu (Section 5.5.7.5).
13. If the H201Ti's alarm contacts are used (connected to a SCADA system), verify the
alarm relays by performing the procedure in Section 7.2.4.
Note: Generally, the SCADA system is connected to the alarm contacts of the Hydran
201Ci Controller.
14. Verify the battery voltage and the other parameters in the Service;Battery
submenu. (Section 5.5.4.3) by performing the procedure in Section 7.2.5. If they
must be adjusted, see Section 7.4.7.
15. Verify the sensor serial number and perform a sensor test, as described in Section
7.2.6.
16. If the analog output is used (connected to a SCADA system), verify it by
performing the procedure in Section 7.2.8.
Note: Generally, the SCADA system is connected to the analog outputs of the H201Ci
Controller.
17. If a USB link is used, verify it by performing the procedure in Section 7.2.9.
Page 198
AC power supply voltage is present on most terminals.
Hydran* 201i Instruction Manual
MA-033