Installing The Ac Power Supply; Verifying The Operation; Verifying The Supervisory Link Communications; Conclusion - GE Hydran 201i Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

8.3.5

Installing the AC Power Supply

1. The power supply cable of the Hydran 201Ci-C must be connected to an external
circuit-breaker in accordance with local wiring regulations.
CAUTION
2. Run the three-wire ac power supply cable through a conduit up to the Hydran
201Ci-C.
3. Connect the cable to the H201Ci-C's L1/L and L2/N terminals, and connect the
E/G wire to the enclosure chassis. For wiring details, see Table D - 8 in Appendix
D.
4. Connect the other end of the cable to the power source.
Note: The earth/ground terminal (E/G) must be connected.
CAUTION

8.3.6 Verifying the Operation

Proceed as described in Section 8.2.1 and Section 8.2.2.

8.3.7 Verifying the Supervisory Link Communications

Verify communications between the Hydran 201Ci-C and the Hydran 201Ti(s) using a
host computer running the Hydran Host software. Proceed as described in Section 8.2.3
and Section 7.2.9.

8.3.8 Conclusion

The installation of the Hydran 201Ci-C is now completed.
Page 128
The circuit-breaker must be located in close proximity to the
equipment and must be easily accessible.
The circuit-breaker must be clearly identified with a label and
marked as the disconnecting device for the equipment.
Never perform high-voltage tests (mega-ohm measurements
using a Megger* instrument) on cables connected to an H201Ti
or a Hydran 201Ci Controller. Never apply high voltages to the
components of a Hydran 201i System, as they are equipped
with surge protection devices that could be damaged by
Megger* tests.
Hydran* 201i Instruction Manual
MA-033
Rev. 14.0, 12-Nov-18