ABB ControlMaster Series Manual page 66

Universal process controllers
Table of Contents

Advertisement

ControlMaster CMF160
Universal process indicator, fieldmount
Digital I/O
Number:
— 6 (standard)
Type:
— User-programmable as input or output
— Minimum input pulse duration – 125 ms
Input:
— Volt-free:
contact open > 10 M
contact closed < 100 K
— 24 V DC
1-signal 15 to 30 V
0-signal –3 to 5 V
— TTL
Low: 0 to 0.8 V
High: 2 to 5 V
— Conforms to IEC 61131-2
Output:
— Open collector output
— 30 V, 100 mA max. switched
— Conforms to IEC 61131-2
Update rate:
— 125 ms
2-Wire transmitter power supply
Number:
— 1 optional
Voltage:
— 24 V DC
Drive:
— 2 loops, 45 mA max.
14
DS/CMF160–EN Rev. B | ControlMaster CMF160 | Universal process indicator, fieldmount
Communications
Note. Only one communications option can be
fitted per indicator.
IrDA service port (standard)
Baud rate:
— Up to 115 kBaud
Distance:
— Up to 1 m (3 ft)
Functions:
— Firmware upgrade
— Configuration upload / download
Ethernet (optional)
Type:
— 10BaseT
Connector:
— RJ 45
Protocols:
— TCP/IP
— HTTP
— MODBUS TCP (Slave)
Web server:
— Built-in, enables remote monitoring using standard
web browsers
Email:
— Can be configured to be sent on the occurrence of
a specified event
— Up to 3 recipients
— Up to 4 trigger sources with configurable tag
MODBUS RTU (optional)
Baud rate:
— Up to 115 kBaud
Isolation:
— Galvanically isolated from the rest of the circuitry,
500 V DC for 1 minute