Mitsubishi Electric 800 Series Instruction Manual page 21

600v class specification inverter
Hide thumbs Also See for 800 Series:

Advertisement

Setting
Pr.
Name
range
Torque control integral
835
0 to 500ms, 9999 9999
time 2
836
Torque setting filter 2
0 to 5s, 9999
837
Torque detection filter 2 0 to 0.1s, 9999 9999
0 to 3, 24, 25,
840
Torque bias selection
9999
600 to 1400%,
841
Torque bias 1
9999
600 to 1400%,
842
Torque bias 2
9999
600 to 1400%,
843
Torque bias 3
9999
844
Torque bias filter
0 to 5s, 9999
845
Torque bias operation time 0 to 5s, 9999
Torque bias balance
846
0 to 10V, 9999
compensation
Fall-time torque bias
847
0 to 400%, 9999
terminal 1 bias
Fall-time torque bias
848
0 to 400%, 9999
terminal 1 gain
Analog input offset
849
0 to 200%
adjustment
Brake operation
850
0 to 2
selection
Control terminal
851
option—Number of
0 to 4096

encoder pulses
Control terminal
852
option—Encoder
0, 1, 100, 101

rotation direction
853
Speed deviation time
0 to 100s

854
Excitation ratio
0 to 100%
Control terminal
855
option—Signal loss
0, 1

detection
Terminal 4 function
858
0, 1, 4, 9999
assignment
0 to 500A,
9999

Torque current/Rated
859
PM motor current
0 to 3600A,
9999

0 to 500A,
Second motor torque
9999

860
current/Rated PM
0 to 3600A,
motor current
9999

Encoder option
862
0, 1

selection
Control terminal
863
option—Encoder pulse
1 to 32767

division ratio
864
Torque detection
0 to 400%
865
Low speed detection
0 to 590Hz
Torque monitoring
866
0 to 400%
reference
867
AM output filter
0 to 5s
Terminal 1 function
868
0 to 6, 9999
assignment
Speed detection
870
0 to 5Hz
hysteresis
Input phase loss
872
0, 1
protection selection
873
Speed limit
0 to 400Hz

874
OLT level setting
0 to 400%
875
Fault definition
0, 1
876
Thermal protector input 0, 1

Speed feed forward control/
877
model adaptive speed control
0 to 2
selection
Speed feed forward
878
0 to 1s
filter
Speed feed forward
879
0 to 400%
torque limit
880
Load inertia ratio
0 to 200 times
Speed feed forward
881
0 to 1000%
gain
Regeneration
882
avoidance operation
0 to 2
selection
Regeneration
883
avoidance operation
300 to 1200V
level
Regeneration avoidance
884
at deceleration detection
0 to 5
sensitivity
Regeneration avoidance
885
compensation frequency
0 to 590Hz, 9999 6Hz
limit value
Regeneration
886
0 to 200%
avoidance voltage gain
888
Free parameter 1
0 to 9999
889
Free parameter 2
0 to 9999
Cumulative power
891
0 to 4, 9999
monitor digit shifted times
892
Load factor
30 to 150%
Initial
Pr.
Name
value
Energy saving monitor
893
reference (motor
capacity)
9999
Control selection during
894
commercial power-
supply operation
9999
Power saving rate
895
reference value
9999
896
Power unit cost
9999
Power saving monitor
897
average time
9999
Power saving cumulative
898
monitor clear
9999
Operation time rate
899
9999
(estimated value)
900
FM terminal calibration ―
9999
901
AM terminal calibration ―
9999
Terminal 2 frequency
setting bias frequency
902
9999
Terminal 2 frequency
setting bias
100%
Terminal 2 frequency
setting gain frequency
903
0
Terminal 2 frequency
setting gain
Terminal 4 frequency
2048
setting bias frequency
904
Terminal 4 frequency
setting bias
1
Terminal 4 frequency
setting gain frequency
1s
905
Terminal 4 frequency
100%
setting gain
Terminal 1 bias
0
frequency (speed)
917
Terminal 1 bias (speed) 0 to 300%
0
Terminal 1 gain
frequency (speed)
918
Terminal 1 gain (speed) 0 to 300%
9999
Terminal 1 bias
command (torque/
magnetic flux)
919
Terminal 1 bias (torque/
9999
magnetic flux)
Terminal 1 gain
command (torque/
0
magnetic flux)
920
Terminal 1 gain (torque/
magnetic flux)
1
Terminal 4 bias
command (torque/
150%
magnetic flux)
932
1.5Hz
Terminal 4 bias (torque/
magnetic flux)
150%
Terminal 4 gain
0.01s
command (torque/
magnetic flux)
933
0
Terminal 4 gain (torque/
magnetic flux)
0Hz
PID display bias
coefficient
934
0

PID display bias analog
value
20Hz
PID display gain
150%
coefficient
935
0

PID display gain analog
1
value
Parameter copy alarm
0
989
release
990
PU buzzer control
0s
991
PU contrast adjustment 0 to 63

992
Parameter for manufacturer setting. Do not set.
150%
994
Droop break point gain 0.1 to 100%, 9999
7 times
Droop break point
995
torque
0%
997
Fault initiation
PM parameter
0
998

initialization
Automatic parameter
999

setting
940VDC
1000
Direct setting selection 0 to 2
Lq tuning target current
1002
0
adjustment coefficient
1003
Notch filter frequency
1004
Notch filter depth
1005
Notch filter width
1006
Clock (year)
100%
9999
9999
9999
100%
Setting
Initial
Pr.
range
value
Rated
0.1 to 55kW

inverter
0 to 3600kW

capacity
0 to 3
0
1007
Clock (month, day)
0, 1, 9999
9999
0 to 500, 9999
9999
0, 1 to 1000h,
9999
9999
0, 1, 10, 9999
9999
0 to 100%, 9999 9999
0 to 590Hz
0Hz
1008
Clock (hour, minute)
0 to 300%
0%
0 to 590Hz
60Hz
0 to 300%
100%
0 to 590Hz
0Hz
0 to 300%
20%
Integral stop selection
0 to 590Hz
60Hz
1015
at limited frequency
PTC thermistor
0 to 300%
100%
1016
protection detection time
Monitor with sign
0 to 590Hz
0Hz
1018
selection
0%
1020
Trace operation selection 0 to 4
1021
Trace mode selection
0 to 590Hz
60Hz
1022
Sampling cycle
100%
Number of analog
1023
channels
0 to 400%
0%
1024
Sampling auto start
1025
Trigger mode selection 0 to 4
0 to 300%
0%
Number of sampling
1026
before trigger
0 to 400%
150%
1027
Analog source selection (1ch)
1028
Analog source selection (2ch)
0 to 300%
100%
1029
Analog source selection (3ch)
1030
Analog source selection (4ch)
0 to 400%
0%
1031
Analog source selection (5ch)
1032
Analog source selection (6ch)
0 to 300%
20%
1033
Analog source selection (7ch)
1034
Analog source selection (8ch)
0 to 400%
150%
1035
Analog trigger channel 1 to 8
Analog trigger
1036
operation selection
0 to 300%
100%
1037
Analog trigger level
0 to 500.00,
1038
Digital source selection (1ch)
9999
9999
1039
Digital source selection (2ch)
0 to 300%
20%
1040
Digital source selection (3ch)
1041
Digital source selection (4ch)
0 to 500.00,
9999
9999
1042
Digital source selection (5ch)
1043
Digital source selection (6ch)
0 to 300%
100%
1044
Digital source selection (7ch)
10
10


1045
Digital source selection (8ch)
100
100


1046
Digital trigger channel
0, 1
1
Digital trigger operation
1047
58
selection
1048
Parameter for manufacturer setting. Do not set.
9999
1049
USB host reset
DC brake judgment time
0.1 to 100%
100%
1072
for anti-sway control
operation
0 to 255, 9999
9999
Anti-sway control
0, 8009, 8109,
1073
0
operation selection
9009, 9109
Anti-sway control
1, 2,10 to 13,
1074
9999
frequency
20, 21, 9999
1075
Anti-sway control depth 0 to 3
0
1076
Anti-sway control width 0 to 3
50 to 150%,
9999
9999
1077
Rope length
0, 8 to 1250Hz
0
1078
Trolley weight
0 to 3
0
1079
Load weight
0 to 3
0
Deceleration time at
1103
emergency stop
2000 to 2099
2000
1106
Torque monitor filter
1107
Running speed monitor filter 0 to 5s, 9999
Excitation current
1108
monitor filter
Speed limit method
1113
selection
Torque command
1114
reverse selection
INVERTER FUNCTION SETTING
Parameter list
Setting
Initial
Name
range
value
101 to 131,
201 to 229,
301 to 331,
401 to 430,
501 to 531,
601 to 630,
101
701 to 731,
801 to 831,
901 to 930,
1001 to 1031,
1101 to 1130,
1201 to 1231
0 to 59, 100 to
159, 200 to 259,
300 to 359,
400 to 459,
500 to 559,
600 to 659,
700 to 759,
800 to 859,
900 to 959,
1000 to 1059,
1100 to 1159,
1200 to 1259,
0
1300 to 1359,
1400 to 1459,
1500 to 1559,
1600 to 1659,
1700 to 1759,
1800 to 1859,
1900 to 1959,
2000 to 2059,
2100 to 2159,
2200 to 2259,
2300 to 2359
0 to 2, 10 to 12 0
0 to 60s
0s
0, 1, 9999
9999
0
0 to 2
0
0 to 9
2
1 to 8
4
0, 1
0
0
0 to 100%
90%
201
1 to 3, 5 to 14,
202
17 to 20, 22 to 24,
32 to 35, 39 to 42,
203
52 to 54, 61, 62,
204
64, 67, 71 to 75,
87 to 98,
205
201 to 213,
206
222 to 227,
230 to 232,
207
235 to 238
208
1
0, 1
0
600 to 1400
1000
1
2
3
4
1 to 255
5
6
7
8
1 to 8
1
0, 1
0
0, 1
0
0 to 10s
3s
0, 1
0
0.05 to 3Hz,
1Hz
9999
0
0
0.1 to 50m
1m
1 to 50000kg
1kg
1 to 50000kg
1kg
0 to 3600s
5s
0 to 5s, 9999
9999
9999
0 to 5s, 9999
9999
0 to 2, 10, 9999 9999
0, 1
1
21