Bosch Rexroth IPC 40.2 Project Planning Manual page 60

Table of Contents

Advertisement

9-6
Software
Note:
After the expiration of the Shutdown Delay Time the
operating system is shut down without safety prompt. Data of
opened application programs without backup are then lost.
Enable Startup Battery Test: If the check box is activated, a test of the
battery pack is carried out after each restart of the system. In error case
an error dialog is generated and a message is sent to the whole system.
The UPS program is still running.
After 12 hours the battery test is automatically repeated:
• If errors don't occur any longer, the battery test is automatically
repeated every 12 hours.
• If an error occurs, an error dialog is generated, a message is send to
the whole system and the UPS program is terminated.
Enable Temp Control: If this check box is activated a continuous
monitoring of the ambient temperature takes place. If +50 °C are
exceeded, a warning window and the LED Temp at the front of the device
flashes. The temperature warning can be deactivated.
For temperatures greater than +65 °C the system is always shut down
and switched off via the UPS logic.
The voltage monitoring is still active after a temperature warning.
Enable Fan Control: If this check box is activated, the existing housing
and CPU fans are monitored. In error case a corresponding message is
indicated and send to the whole system.
Enable Voltage Control: If the check box is activated, the internal supply
voltages are monitored. In error case a corresponding message is
indicated and send to the whole system.
No Powerdown on Shortbreak: If the check box is activated,
interruptions of the supply voltage up to 5 sec are permissible and do not
influence the operation. Only for voltage breakdowns greater than 5 sec
the UPS logic is started and the shutdown of the system is introduced.
UPS Off, Disable UPS: The function UPS Off, Disable UPS deactivates
the UPS monitoring and the delay, when the power supply unit is switched
off:
• If a voltage breakdown occurs, the PC switches immediately off.
• After a conventional shutdown of the system, there's no waiting time of
approximately 60 sec until the power supply unit switches off.
This function shortens the waiting time during commissioning and
software installation. However, this check box must not be activated in the
normal mode.
Loss of data!
If this check box is activated, a proper system
shutdown is no longer possible during a voltage
breakdown. The device switches off immediately!
CAUTION
IPC 40.2
DOK-SUPPL*-IPC*40.2***-PR02-EN-P