Huawei UPS5000-E Series Quick Manual

Huawei UPS5000-E Series Quick Manual

50 kva power modules
Hide thumbs Also See for UPS5000-E Series:

Advertisement

UPS5000-E-(550 kVA-600 kVA)
Quick Guide (50 kVA Power Modules)
Issue: 08
Part Number: 31507658
Date: 2019-10-16
1
Overview
UPS Model
UPS5000-E-600K-SM/FM
UPS5000-E-600K-SM
(1) Power modules
(2) Control module
(3) Optional card slot
(4) Power distribution module
covers
(5) Maintenance bypass switch
(6) Bypass module
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
Weight
1090 kg
UPS5000-E-600K-FM
(1) Power modules
(3) Optional card slot
(5) Output switch
(7) Maintenance
bypass switch
(9) Bypass module
1
Dimensions (H x W x D)
2000 mm x 1400 mm x 850 mm
(2) Control module
(4) Mains input switch
(6) Power distribution
module covers
(8) Bypass input switch

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E Series

  • Page 1 UPS5000-E-(550 kVA-600 kVA) Quick Guide (50 kVA Power Modules) Issue: 08 Part Number: 31507658 Date: 2019-10-16 Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved. Overview Dimensions (H x W x D) UPS Model Weight UPS5000-E-600K-SM/FM 1090 kg 2000 mm x 1400 mm x 850 mm...
  • Page 2: Installing The Ups

    UPS faults are beyond the warranty scope. 4. This document describes how to install a single UPS. For details about how to install parallel systems, contact Huawei technical support. Installing the UPS Determining the UPS Installation Position NOTE 1.
  • Page 3 Securing the UPS • Floor mounting: Use eight M12x60 expansion bolts to secure the cabinet to the ground. • Channel steel mounting: Use eight M12x60 common bolts to secure the cabinet to channel steels. (1) Cabinet mounting holes (ground installation mode) (2) Cabinet mounting holes (channel steel installation mode) Install the front, rear, left, and right anchor baffle plates...
  • Page 4: Connecting Cables

    Connecting Cables 1. This document describes cable routing by removing the top cover when there are two mains inputs. 2. In the case of single mains, you do not need to connect bypass input power cables and remove short-circuit copper bars. UPS Cable Connection Reference •...
  • Page 5 Scenario 1: Routing Cables from the Top 1. Open the front door of the bypass cabinet, 2. Remove the cable covers from the top of the and remove front power distribution cabinet. Then remove the beam, which is an covers. optional step.
  • Page 6 5. Connect the mains input power cable. 6. Connect the output power cable. 7. Connect bypass input power cables. 8. Connect the battery cable.
  • Page 7 9. Connect signal cables. Route a neutral wire from the middle of the positive and negative battery strings. Take a battery string consisting of 40 batteries as an example. A neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries.
  • Page 8: Installation Verification

    Installation Verification 1. Check that there is no foreign matter in the cabinet. (1) Switches (2) Mains input wiring copper bars (3) Battery input wiring copper bars (4) Output wiring copper bars (5) Bypass input wiring copper bars (6) Cabinet rear 4.
  • Page 9: Powering On And Starting The Ups

    Close the upstream bypass and mains input switches. (Full configuration model) Close the UPS bypass input switch, output switch, and mains input switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 10 3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault. 4. View the system running status diagram on the MDU to check that the UPS is working in bypass mode.
  • Page 11: Shutting Down The Ups

    Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2. After confirming that the battery strings are properly connected, turn on the battery string input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each battery string and then turn on the general circuit breaker between battery strings and the UPS.
  • Page 12 Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: http://support.huawei.com/enterprise http://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...

This manual is also suitable for:

Ups5000-e-600k-fmUps5000-e-600k-sm

Table of Contents