Instructions for data set changeover
Using drive data set changeover (DDS), motor data sets (MDS, p0186) and encoder data
sets (EDS, p0187 to p0189) can be changed over. The following table shows when the
reference bit (r2684.11) or the status of the adjustment with absolute encoders (p2507) is
reset.
In the following cases, when a DDS changeover takes place, the actual position value
becomes invalid (p2521 = 0) and the reference point (r2684.11 = 0) is reset.
● The EDS that is effective for the position control changes.
● The encoder assignment changes (p2502).
● The mechanical relationships change (p2503...p2506)
With absolute encoders, the status of the adjustment (p2507) is also reset, if the same
absolute encoder is selected for the position control although the mechanical relationships
have changed (p2503 ... p2506).
In operating mode, a fault (F07494) is also output.
The following table contains a few examples for data set changeover. The initial data set is
always DDS0.
Table 7- 6
DDS changeover without load gear position tracking
DDS p0186
p0187
(MDS)
(encoder_1)
0
0
EDS0
1
0
EDS0
2
0
EDS0
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
p0188
p0189
(encoder_2)
(encoder_3)
EDS1
EDS2
EDS1
EDS2
EDS1
EDS2
Encoder
Mechanical
for position
conditions
control
4)
p2502
p2504/
p2505/
p2506 or
p2503
encoder_1 xxx
encoder_1 xxx
encoder_1 yyy
Function modules
7.8 Basic positioner
Load gear
Changeover response
position
tracking
Deactivated
---
Deactivated
Changeover during
pulse inhibit or
operation has no
effect
Deactivated
Pulse inhibit: Actual
position value
processing is newly
initiated
1)
reference bit
reset.
Operation:
Fault is output. Actual
position value
processing is newly
initiated
1)
reference bit
reset.
and
is
2)
and
is
2)
467