Rexroth IndraDrive
Selection
460
i = 0.52
380
AC(200...240)V
DST**/*/240-460
0
200
220
DOK-INDRV*-ADDCOMP****-PR02-EN-P
Select an autotransformer suited to both the line voltage and the power
requirements of the system.
Proceed with the selection as follows:
⇒
Determine the rating group using the required rated line voltage range
in the diagram "Classification of the three-phase alternating current
autotransformers and then locate the transformer ratio "i".
Calculate the actual transformer output voltage using the rated line
⇒
voltage and the transformation ratio "i".
⇒
Check the drive data. The output voltage of the transformer has an
effect on the drive data.
Select a three-phase autotransformer corresponding to the required
⇒
connected load.
i = 1.08
AC(480...500)V
DST**/*/500-460
AC(480...580)V
DST**/*/580-460
240
480
500
520
Fig. 4-2:
Classification of three-phase autotransformers in rating groups
i = 1.26
AC(570...690)V
DST**/*/690-460
540
560
580
600
Input voltage in V of the transformer
Transformers
i = 1.50
620
640
660
680
Ap5087f1.fh7
4-3
700