Modules Switchable By; Ep-19 Xx - GE RSTi-EP Functional Safety Manual

Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

Chapter 1. Introduction
1.2
Modules Switchable by EP-19xx
Safely switchable output modules:
EP-2214
EP-2614
EP-2634
EP-2218
EP-225F
EP-5422
EP-5442
EP-4164
EP-4264
In case a N-logic output module is positioned within a safety segment the connected load needs to
be switched against +24 V Safe.
The relay output modules EP-2714 and EP-2814are not safely switchable, therefore they must not
switch any safety function.
The digital counter module EP-5111 will not be switched since it is supplied via the input current path.