Power saving mode
04
enable/disable
05
Battery type
Auto restart when overload
06
occurs
Auto restart when over
07
temperature occurs
Output voltage
*This setting is only
available when the inverter
08
is in standby mode (Switch
off).
Output frequency
*This setting is only
09
available when the inverter
is in standby mode (Switch
off).
Number of series
10
batteries connected
Saving mode disable (default)
If disabled, no matter connected load is low or high, the on/off status of
inverter output will not be effected.
Saving mode enable
If enabled, the output of inverter will be off when connected load is pretty
low or not detected.
AGM (default)
Flooded
Lithium (only suitable when communicated with BMS)
User-Defined
If "User-Defined" is selected, battery charge voltage and low DC cut-off
voltage can be set up in program 19, 20 and 21.
User-Defined 2(suitable when lithium battery without BMS
communication)
If "User-Defined 2" is selected, battery charge voltage and low DC cut-off
voltage can be set up in program 19, 20 and 21. It is recommended to set to
the same voltage in program 19 and 20(full charging voltage point of lithium
battery). The inverter will stop charging when the battery voltage reach this
setting.
Restart disable (default)
Restart disable (default)
230V (default)
240V
50Hz (default)
(e.g. Showing batteries are connected in 4 series)
17
Restart enable
Restart enable
220V
208V
60Hz
Need help?
Do you have a question about the SPF 5000 ES and is the answer not in the manual?
Questions and answers
spf 5000, for my input from utility, I have 2 lines of 120 and 1 neutral and ground. Do I join the 2 lines together?
No, you should not connect two 120V lines together for the Growatt SPF 5000 ES inverter. For 240V loads, connect Line 1 and Line 2 directly from the inverter. Each line provides 120V relative to neutral, and together they supply 240V. Connecting two 120V lines improperly can cause damage or unsafe conditions.
This answer is automatically generated