Growatt SPF 3500 ES User Manual

Growatt SPF 3500 ES User Manual

Off grid solar inverter

Advertisement

User Manual
Off Grid Solar Inverter
SPF 3500 ES
SPF 5000 ES
Version: 4.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SPF 3500 ES and is the answer not in the manual?

Questions and answers

Summary of Contents for Growatt SPF 3500 ES

  • Page 1 User Manual Off Grid Solar Inverter SPF 3500 ES SPF 5000 ES Version: 4.0...
  • Page 2: Table Of Contents

    Table Of Contents Information on this Manual ..............................1 Validity ..............................1 Scope ................................. 1 Target Group ............................. 1 Safety Instructions ........................... 1 Introduction ................................... 2 Features ..............................2 Product Overview ............................3 Installation ..................................... 4 Unpacking and Inspection ........................4 Preparation ...............................
  • Page 3: Information On This Manual

    Information on this Manual Validity This manual is valid for the following devices: SPF 3500 ES SPF 5000 ES Scope This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations.
  • Page 4: Introduction

    Introduction Hybrid Power System This is a multifunctional off grid solar inverter, integrated with a MPPT solar charge controller, a high frequency pure sine wave inverter and a UPS function module in one machine, which is perfect for off grid backup power and self-consumption applications.
  • Page 5: Product Overview

    Product Overview 1. LCD display 2. Status indicator 3. Charging indicator 4. Fault indicator 5. Function buttons 6. AC input 7. WiFi/GPRS communication port 8. USB communication port 9. BMS communication port (support CAN/RS485 protocol) 10. RS485 communication port (for expansion) 11.
  • Page 6: Installation

    Installation Unpacking and Inspection Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items in the package: The unit x 1 User manual x 1 Communication cable x 1 Current sharing cable x 1 Parallel communication cable x 1 Note: The Software CD is no longer provided, if necessary, please download it from the official website...
  • Page 7: Battery Connection

    2. Connect all battery packs as units requires. It’s suggested to connect at least 200Ah capacity battery for SPF 3500 ES /SPF 5000 ES. 3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2Nm.
  • Page 8: Lithium Battery Connection

    Lithium Battery Connection If choosing lithium battery for SPF 3500 ES /SPF 5000 ES, you are allowed to use the lithium battery only which we have configured. There're two connectors on the lithium battery, RJ45 port of BMS and power cable.
  • Page 9 LCD setting To connect battery BMS, need to set the battery type as “LI” in Program 05. After set “LI” in Program 05, it will switch to Program 36 to choose communication protocol. You can choose RS485 communication protocol which is from L01 to L50, and you can also choose CAN communication protocol which is from L51 to L99.
  • Page 10 Default 20%, 5%~50% Settable Note: Any questions about communicating with BMS, please consult with Growatt. Communicating with battery BMS in parallel system If need to use communicate with BMS in a parallel system, you should make sure to connect the BMS communication cable between the battery and one inverter of the parallel system.
  • Page 11: Ac Input/Output Connection

    AC input. The recommended spec of AC breaker is 40A for SPF 3500 ES and 50A for SPF 5000 ES. CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
  • Page 12: Pv Connection

    WARNING! It’ very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below. Torque value Model Wire Size SPF 3500 ES 1 * 12 AWG 1.2-1.6 Nm SPF 5000 ES 1 * 12 AWG 1.2-1.6 Nm...
  • Page 13: Communication Connection

    Final Assembly After connecting all wiring, please put bottom cover back by screwing two screws as shown below. Communication Connection Please use supplied communication cable to connect to inverter and PC. Follow on-screen instruction to install the monitoring software. For the detailed software operation, please check user manual of software. The monitoring software is downloadable from our website www.ginverter.com.
  • Page 14: Operation

    Operation Power ON/OFF Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit. Operation and Display Panel The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
  • Page 15: Lcd Display Icons

    LCD Display Icons Icon Description AC Input Information AC input icon Indicate AC input power, AC input voltage, AC input frequency, AC input current Indicate AC power loads in bypass PV Input Information PV input icon Indicate PV power, PV voltage, PV current, etc Output Information Inverter icon Indicate...
  • Page 16 In AC mode, battery icon will present Battery Charging Status Status Battery voltage LCD Display <2V/cell 4 bars will flash in turns. Bottom bar will be on and the other three bars Constant Current 2 ~ 2.083V/cell will flash in turns. mode / Constant Bottom two bars will be on and the other two bars 2.083 ~ 2.167V/cell...
  • Page 17: Lcd Setting

    Maximum charging current: set total charging current for solar and utility chargers. SPF 3500 ES: Default 60A, 10A~80A Settable (Max. charging current = SPF 5000 ES: Default 60A, 10A~100A Settable utility charging current + (If LI is selected in Program 5, this program can’t be set up)
  • Page 18 Saving mode disable (default) If disabled, no matter connected load is low or high, the on/off status of inverter output will not be effected. Power saving mode enable/disable Saving mode enable If enabled, the output of inverter will be off when connected load is pretty low or not detected.
  • Page 19 Note: If setting value in Program 02 is smaller than that in Program 11, SPF 3500 ES :Default 30A, 0A~60A Settable the inverter will apply SPF 5000 ES :Default 30A, 0A~80A Settable charging current from Program 02 for utility...
  • Page 20 Low DC cut-off voltage. Default 42.0V, 40.0V~48.0V Settable If self-defined is selected in program 5, this program can When reach Low DC cut-off voltage: be set up. 1) If battery power is only power source available, inverter will shut down. Low DC cut-off voltage will 2) If PV energy and battery power are available, inverter will charge be fixed to setting value no...
  • Page 21 Battery equalization enable Battery equalization disable(default) Battery equalization If “Flooded” or “User-Defined” is selected in program 05, this program can be set up. Battery equalization voltage Default 58.4V, 48.0V~58.4V Settable Default 60min, 5min~900min Battery equalized time Settable Default 120min, 5min~900min Battery equalized timeout Settable Default 30days, 1 days~90 days...
  • Page 22: Display Information

    Display Information The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: voltage, frequency, current, power, firmware version. Setting Information LCD display ① AC Input voltage ② Output voltage ③...
  • Page 23: Operating Mode Description

    Operating Mode Description Operation mode Description LCD display Standby mode / Power Charging by utility and PV Charging by utility energy. saving mode Note: *Standby mode: The No output is inverter is not turned on yet but at this time, the inverter can supplied by the charge battery without AC unit but it still...
  • Page 24: Parallel Installation Guide

    Parallel Installation Guide Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 6 units. 2. Maximum 6 units work together to support 3-phase equipment. Four units support one phase maximum. Note: If the package includes share current cable and parallel cable, the inverter is default supported parallel operation.
  • Page 25 Step 3: Remove two screws as below chart and remove 2-pin and 14-pin cables. Take out the board under the communication boards. Step 4: Remove two screws as below chart to take out cover of parallel communication. Step 5: Install new parallel board with 2 screws tightly. Step 6: Re-connect 2-pin and 14-pin to original position of parallel board, and re-connect 2-pin and 6-pin to original position of communication board.
  • Page 26 The cable size of each inverter is shown as below Recommended battery cable and terminal size for each inverter: Ring terminal: Model Wire Size Torque value SPF 3500 ES 1 * 4 AWG 2-3 Nm SPF 5000 ES 1 * 2 AWG 2-3 Nm WARNING: Be sure the length of all battery cables is the same.
  • Page 27: Parallel Operation In Single Phase

    250A/230VAC 300A/230VAC Note1: You can use 40A breaker for SPF 3500 ES and 50A for SPF 5000 ES for only 1 unit, and each inverter has a breaker at its AC input. Note2: Regarding three phase system, you can use 4 poles breaker, the rating is up to the current of the phase which has the maximum units.
  • Page 28 Three inverters in parallel: Power Connection Communication Connection Four inverters in parallel: Power Connection Communication Connection Five inverters in parallel:...
  • Page 29 Power Connection Communication Connection Six inverters in parallel: Power Connection Communication Connection...
  • Page 30: Parallel Operation In Three Phase

    Parallel Operation in Three Phase WARNING! All inverters must be connected to the same batteries and ensure each group of cables from the inverters to the batteries in the same length. One inverter in each phase: Power Connection Communication Connection Two inverters in one phase and only one inverter for the remaining phases: Power Connection Communication Connection...
  • Page 31 Two inverters in two phases and only one inverter for the remaining phase: Power Connection Communication Connection Three inverters in one phase and only one inverter for the remaining two phases: Power Connection Communication Connection...
  • Page 32 Two inverters in each phase: Power Connection Communication Connection Three inverters in one phase, two inverters in second phase and one inverter for the third phase: Power Connection Communication Connection...
  • Page 33: Pv Connection

    Four inverters in one phase and one inverter for the other two phases: Power Connection Communication Connection WARNING: Do not connect the current sharing cable between the inverters which are in different phases. Otherwise, it may damage the inverters. PV Connection Please refer to user manual of single unit for PV Connection on Page 10.
  • Page 34 LCD display in Master unit LCD display in Slave unit Note: Master and slave units are randomly defined. Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility at the same time.
  • Page 35: Fault Reference Code

    Fault Reference Code Fault Code Fault Event Icon on Fan is locked Over temperature Battery voltage is too high Battery voltage is too low Output short circuited Output voltage is too high. Overload time out Bus voltage is too high Bus soft start failed Over current or surge Bus voltage is too low...
  • Page 36: Warning Indicator

    Warning Indicator Warning Warning Event Audible Alarm Icon Code flashing Fan is locked when inverter is on. Beep 3 times every second Beep once every second Over temperature Beep once every second Battery is over-charged Beep once every second Low battery Beep once every 0.5 second Overload Output power derating...
  • Page 37: Battery Equalization

    Battery Equalization Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalizationalso helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery.
  • Page 38: Specifications

    Specifications Table 1 Line Mode Specifications INVERTER MODEL SPF 3500 ES SPF 5000 ES Input Voltage Waveform Sinusoidal (utility or generator) Nominal Input Voltage 230Vac Low Loss Voltage 170Vac±7V (UPS); 90Vac±7V (Appliances) Low Loss Return Voltage 180Vac±7V (UPS); 100Vac±7V (Appliances) High Loss Voltage 280Vac±7V...
  • Page 39 Table 2 Inverter Mode Specifications INVERTER MODEL SPF 3500 ES SPF 5000 ES Rated Output Power 3.5KVA/3.5KW 5KVA/5KW Pure Sine Wave Output Voltage Waveform 230Vac±5% Output Voltage Regulation Output Frequency 50Hz Nominal Output Current 15.2A 21.7A 80A/ 300μs Max. Output Fault Current/ Duration Max.
  • Page 40 Table 3 Charge Mode Specifications Utility Charging Mode INVERTER MODEL SPF 3500 ES SPF 5000 ES Charging Algorithm 3-Step 60Amp(@V =230Vac) 80Amp(@V =230Vac) Max. AC Charging Current 58.4Vdc Bulk Charging Flooded Battery Voltage AGM / Gel Battery 56.4Vdc Floating Charging Voltage...
  • Page 41: Trouble Shooting

    Trouble Shooting Problem LCD/LED/Buzzer Explanation What to do LCD/LEDs and buzzer Unit shuts down The battery voltage is too low . 1. Re-charge battery. will be active for 3 Automatically during seconds and then (<1.91V/Cell) 2. Replace battery. startup process. complete off.
  • Page 42 1. If you connect to a lithum battery without communication, check whether the voltage points of the program 19 and 21 are too high Fault code 08 Bus voltage is too high. for the lithum battery. 2. Restart the unit, if the error happens again, please return to repair center.