3.3.4

Connecting separately shipped transport units

Description
An accessories kit is provided with each transport unit for mechanically connecting the sub-
cabinet units. The table below shows the content of this accessories kit for connecting the
cabinet units.
Table 3- 1
Content of the accessories kit for connecting the cabinet units
Quantity
Material
1 x
Sealing strip
3 x
Outer cabinet connectors
including Mounting material
3 x
Inner cabinet connectors
including Mounting material
Mounting
1. Attach the sealing strip to the cabinet frames of the cabinets to be connected.
2. Push the cabinets together, they must completely come together at the front and the rear
sides. The distance between the cabinets must be approximately 3 mm.
3. Mount the cabinet connectors at the outside and inside corresponding to the following
drawing.
4. If necessary, reattach the protective covers and doors. The ground connections must also
be attached to the doors.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Fig.
Notes
The sealing strip must be attached to the cabinets
before connecting them together.
The cabinet connector is fitted and screwed on from
the outside.
Tightening torque: 9 Nm
The cabinet connector is fastened with 4 screws.
Tightening torque: 5 Nm
Mechanical installation
3.3 Mounting
51