Huawei SUN2000-3KTL-M0 User Manual page 58

Hide thumbs Also See for SUN2000-3KTL-M0:
Table of Contents

Advertisement

SUN2000-(3KTL-12KTL)-M0
User Manual
Alar
Alarm Name
m ID
2034
Grid Overvoltage
Unbalanced Grid
2035
Voltage
Issue 01 (2018-12-30)
Alarm
Possible Cause
Severity
Major
The power grid voltage is
beyond the upper threshold or
the overvoltage duration
exceeds the value specified by
HVRT.
The difference between grid
Major
phase voltages exceeds the
upper threshold.
Copyright © Huawei Technologies Co., Ltd.
7 Maintenance
Troubleshooting Suggestion
1. If the alarm occurs
occasionally, the power grid
may be abnormal temporarily.
The SUN2000 automatically
recovers after detecting that
the power grid becomes
normal.
2. If the alarm occurs frequently,
check whether the grid voltage
is within the acceptable range.
If no, contact the local power
operator. If yes, log in to the
mobile phone app,
SmartLogger, or NMS to
modify the grid overvoltage
protection threshold with the
consent of the local power
operator.
3. Check whether the peak
voltage of the power grid is
too high. If the fault persists
and cannot be rectified for a
long time, contact the power
operator.
1. If the alarm occurs
occasionally, the power grid
may be abnormal temporarily.
The SUN2000 automatically
recovers after detecting that
the power grid becomes
normal.
2. If the alarm occurs frequently,
check whether the grid voltage
is within the acceptable range.
If no, contact the local power
operator.
3. If the fault persists for a long
time, check the connection
between the AC switch and the
output power cable.
52

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents