4.1.2 Katharometer Analyzer Panel – Fig. 4.2
Refer also to IM/6517-6518 for further details.
Note. The panel may be located in the hazardous area (Zone 0, 1 or 2) of the application plant in a sheltered interior
environment.
Avoid a location that subjects the katharometer unit to direct sunlight. When two katharometer panels are used locate them in
positions that have the same ambient temperature.
The katharometer unit is fixed to the panel that has fixing holes at each corner for mounting on a suitable vertical surface close to the
sample tapping point. The installation dimensions for the panel are shown in Fig. 4.2.
Dimensions in mm (in.)
See
Note 1
Note 1. Coupling for
Ø6 (0.24) Tube (006548000) or
Ø8 (0.31) Tube (006540203)
610 (24)
572 ±0.3 (22.5±0.01)
Gland for Ø7 to Ø10.5 (0.28 to 0.41) Cable
10
(0.39)
Note 2. Terminal box fitted only to
systems equipped with optional low
flow alarm.
Fig. 4.2 Installation Dimensions –
Model 006540 203 or 006548 000 Katharometer Analyzer Panel
4 MECHANICAL INSTALLATION...
19 (0.75)
Outlet
B10
KATHEROMETER
N
O
1
See
Note 3
B12
LOW FLOW
ALARM KATH N
O
1
See
Note 2
Note 3. A different type of flow gauge is
fitted to systems not equipped with the
optional low flow alarm – see Fig 6.1.
148 (5.83)
38 (1.5)
See
Note 1
4 Fixing
Holes Ø10 (0.39)
9