(g) The cabling of 200m (656.2ft.) or longer distance may produce
leakage current depending on the capacity between lines and
result in an accident.
(h) As a countermeasure against the power surge due to lightning,
separate the AC wiring and DC wiring and connect a surge
absorber for lightning as shown in (i) of item (1).
Failure to do so increases the risk of I/O device failure due to
lightning.
(3) Grounding
(a) Carry out the independent grounding if possible. (Grounding
resistance 100 or less.)
(b) If the independent grounding is impossible, carry out the
shared grounding (2) as shown below.
Other
Programmable
device
controller
Class 3
grounding
(1) Independent grounding.....Best
(c) Use thick cables up to 2mm
to the programmable controller as much as possible so that
the ground cable can be shortened.
(d) If a malfunction occurs due to earthling, separate either LG or
FG of the base module, the device combination, or all the
connection from the earthling.
Other
Programmable
device
controller
Class 3
grounding
(2) Shared grounding.....Good
54
Programmable
controller
(3) Common grounding.....Not allowed
2
. Bring the grounding point close
Other
device