Error
Error
Code
Massage
(D9008)
"PARAMET
ER
ERROR"
11
(Checked
at power on
and at
STOP/
PAUSE
RUN.)
"MISSING
END INS"
12
(Checked
at STOP
RUN.)
"CAN'T
EXECUTE
(P)"
13
(Checked
at
execution
of
instruction.)
Table 6.1 Error Code List (Continue)
Detailed
Error
CPU
Code
States
(D9091)
Either of settings of the
remote RUN/PAUSE
contact point by
parameters, operation
115
mode at occurrence of
error, annunciator
indication mode, or
STOP RUN indication
mode is incorrect.
STOP
The MNET-MINI
automatic refresh setting
116
by parameters is
incorrect.
Timer setting by
117
parameters is incorrect.
Counter setting by
118
parameters is incorrect.
The
121
instruction is not given in
the main program.
The
STOP
instruction is not given in
122
the sub program if the
sub program is set by
parameters.
The same device number
is used at two or more
steps for the pointers (P)
131
and interrupt pointers (I)
used as labels to be
specified at the head of
jump destination.
STOP
Label of the pointer (P)
specified in the
CALL CALLP
132
LEDA/B FCALL
LEDA/BBREAK
is not provided before the
END instruction.
Error and Cause
(
)
END
FEND
(
)
END
FEND
,
,
CJ
SCJ
,
,
,
JMP
or
instruction
95
Corrective Action
Read parameters in the
CPU memory, check the
contents, make
necessary corrections
and write them again to
the memory.
Write the
instruction
END
at the end of the main
program.
Write the
instruction
END
at the end of the sub
program.
Eliminate the same
pointer numbers
provided at the head of
jump destination.
Read the error step using
a peripheral device,
check contents and insert
a jump destination
pointer (P).